3. OPERATION PRINCIPLES
GEK-98514B
BUS1000 Busbar Protection
3-1
3.
3.
3.
3.
OPERATION PRINCIPLES
OPERATION PRINCIPLES
OPERATION PRINCIPLES
OPERATION PRINCIPLES
3.1.
BASIC PRINCIPLE
The measurement method relies on Kirchhoff´s current law.
This law states that the vectorial sum of all currents flowing into a closed area must be zero. This law
applies, in the first instance, to dc current. It applies to ac current for instantaneous values. Thus, the sum of
the currents in all feeders of a busbar must be zero at any instant in time.
I
1
I
2
I
3
. . . .
I
n
Figure 3.1. Busbar with “n” feeders
Assuming that the currents I
1
, I
2
,I
3
... I
n
flow in the feeders ( Fig 3.1) connected to the busbar, the following
equation applies in the fault-free condition ( the currents flowing towards the busbar are defined as positive,
and the currents flowing away from the busbar as negative ) :
I
1
+ I
2
+ I
3
... + I
n
= 0
If this equation is not fulfilled, then there must be some other-impermissible-path through which a current
flows. This means that there is a fault in the busbar region.
This law is superior, as the basis for busbar protection, to any other known way of measurement. A single
quantity, the sum of currents, characterises and can be used to detect faulty conditions. This sum of all
currents can be formed at any time and if formed as such, using instantaneous current values, full use of
above law can be made. Above law is always valid, whereas with a comparison of only the zero crossing
points of the currents or of the current directions may involve phase displacements that would have to be
considered accordingly. For instance, in a fault-free three-phase load, the instants of zero current are
displaced by 50º or 120º with respect to e. Unbalanced load may produce other displacements. The sum of
the currents, on the other hand, remains constantly zero as long as no currents flow through some other
path due to a fault.
The above considerations apply strictly to the primary conditions in a high-voltage switching station.
Protection systems, however, cannot carry out direct measurements of currents in high-voltage systems.
Protection equipment measurement systems, performing the current comparisons, are connected through
current transformers. The secondary windings provide the currents scaled down according to the
transformation ratio while retaining the same phase relation. Furthermore, the current transformers, due to
the isolation of their secondary circuits from the high-voltage system and by appropriate grounding
measures, can keep dangerous high voltages away from the protection system.
The current transformers are an integral part of the whole protection system and their characteristics are an
important factor for the correct operation of the protection. Their physical locations mark the limits of the
protection zone covered by the protection system.
Содержание BUS1000
Страница 6: ......
Страница 8: ......
Страница 27: ...5 HARDWARE DESCRIPTION GEK 98514B BUS1000 Busbar Protection 5 3 Figure 7 1 BBD RACK Figure 7 2 BTR RACK ...
Страница 28: ...5 HARDWARE DESCRIPTION 5 4 BUS1000 Busbar Protection GEK 98514B Figure 7 4 BAR RACK Figure 7 5 BFR RACK ...
Страница 34: ...5 HARDWARE DESCRIPTION 5 10 BUS1000 Busbar Protection GEK 98514B ...
Страница 36: ...6 RECEIVING HANDLING AND STORAGE 6 2 BUS1000 Busbar Protection GEK 98514B ...
Страница 54: ...8 FINAL INSTALLATION AND COMMISSIONING 8 4 BUS1000 Busbar Protection GEK 98514B ...
Страница 56: ...9 TESTS AND PERIODICAL MAINTENANCE 9 2 BUS1000 Busbar Protection GEK 98514B ...
Страница 57: ...10 FIGURES GEK 98514B BUS1000 Busbar Protection 10 1 10 10 10 10 FIGURES FIGURES FIGURES FIGURES ...
Страница 66: ...10 FIGURES 10 10 BUS1000 Busbar Protection GEK 98514B ...
Страница 70: ...11 DIMENSIONS 11 4 BUS1000 Busbar Protection GEK 98514B FIGURE 19 POWER SUPPLY OR THYRITE BOXES 226B2211F18 ...
Страница 71: ...11 DIMENSIONS GEK 98514B BUS1000 Busbar Protection 11 5 FIGURE 20 BREAKER BLOCK DIAGRAM 226B2211F23 ÿ ÿ ÿ ÿ ÿ ...
Страница 74: ...11 DIMENSIONS 11 8 BUS1000 Busbar Protection GEK 98514B FIGURE 23 CABINET 226B2211F21 ...
Страница 104: ...13 SCHEMATICS DOUBLE BUSBAR 13 16 BUS1000 Busbar Protection GEK 98514B ...
Страница 107: ...13 SCHEMATICS DOUBLE BUSBAR GEK 98514B BUS1000 Busbar Protection 13 19 16 TEST UNIT ZONES A B 226B6429F16 ...
Страница 121: ...13 SCHEMATICS DOUBLE BUSBAR GEK 98514B BUS1000 Busbar Protection 13 33 31 POWER SUPPLY AUXILIARY CIRCUITS 226B6429F31 ...
Страница 123: ...13 SCHEMATICS DOUBLE BUSBAR GEK 98514B BUS1000 Busbar Protection 13 35 43 SIGNALLING CONTACT OUTPUTS 226B6429F43 ...
Страница 124: ...13 SCHEMATICS DOUBLE BUSBAR 13 36 BUS1000 Busbar Protection GEK 98514B CABINETS INTERCONNECTIONS 226B6429F44 ...