5. HARDWARE DESCRIPTION
GEK-98514B
BUS1000 Busbar Protection
5-7
Operation level adjustment of the breaker failure unit (FIG. 11)
It is carried out by means of microswitches placed in the front part of the breaker failure board (SFI).
The minimum adjustment (all the microswitches placed at the left), is 0.2 A on the 1 A side, plus the number
corresponding to every microswitch located to the right. The unit adjustment ranges from 0.2 to 3.3 A on the 1
A side, in 0.1 steps.
Operation time adjustment of the breaker failure unit (FIG. 11)
It is carried out by means of microswitches placed in the front part of the breaker failure board (SFI).
The minimum adjustment (all the microswitches placed at the left) is 0.2 s, plus the number corresponding to
every microswitch, positioned to the right. The adjustment ranges from 0.1 to 1.6 s in 0.1 steps.
Operation level adjustment of the overcurrent unit (FIG. 11)
Two versions are available for the operation level of the overcurrent unit. In the first case, the level depends
on the level adjustment of the breaker failure unit, and in the second the level is totally independent.
Dependent adjustment:
It is done by means of microswitches placed in the front part of the breaker failure board (SFI).
The minimum adjustment (all the microswitches placed at the left) is 0.25 times the adjustment of the breaker
failure unit, plus the number corresponding to every microswitch, positioned to the right. The adjustment
ranges from 0.25 to 1 time, in 0.05 steps.
Independent adjustment:
The same as the operation level adjustment of the breaker failure unit.
Bus coupling timer adjustment
It is done by means of microswitches placed in the front part of the switching module (MDF).
The minimum adjustment (all the microswitches placed at the left) is 0.2 s, plus the number corresponding to
every microswitch, positioned to the right. The adjustment ranges from 0.2 to 1.7 s, in 0.1 steps.
Breaker failure trip signalling (FIG. 11)
It is done by means of a red LED placed in the front part of the boards, in every breaker failure unit.
This signalling is continuous and the reset is achieved manually through a push-button placed in the front
part of the board.
Operation signalling of the overcurrent unit (FIG. 11)
It is done by means of a red LED placed in the front part of the boards, in every breaker failure unit.
This signalling is not continuous and stops signalling when the unit is reset.
Содержание BUS1000
Страница 6: ......
Страница 8: ......
Страница 27: ...5 HARDWARE DESCRIPTION GEK 98514B BUS1000 Busbar Protection 5 3 Figure 7 1 BBD RACK Figure 7 2 BTR RACK ...
Страница 28: ...5 HARDWARE DESCRIPTION 5 4 BUS1000 Busbar Protection GEK 98514B Figure 7 4 BAR RACK Figure 7 5 BFR RACK ...
Страница 34: ...5 HARDWARE DESCRIPTION 5 10 BUS1000 Busbar Protection GEK 98514B ...
Страница 36: ...6 RECEIVING HANDLING AND STORAGE 6 2 BUS1000 Busbar Protection GEK 98514B ...
Страница 54: ...8 FINAL INSTALLATION AND COMMISSIONING 8 4 BUS1000 Busbar Protection GEK 98514B ...
Страница 56: ...9 TESTS AND PERIODICAL MAINTENANCE 9 2 BUS1000 Busbar Protection GEK 98514B ...
Страница 57: ...10 FIGURES GEK 98514B BUS1000 Busbar Protection 10 1 10 10 10 10 FIGURES FIGURES FIGURES FIGURES ...
Страница 66: ...10 FIGURES 10 10 BUS1000 Busbar Protection GEK 98514B ...
Страница 70: ...11 DIMENSIONS 11 4 BUS1000 Busbar Protection GEK 98514B FIGURE 19 POWER SUPPLY OR THYRITE BOXES 226B2211F18 ...
Страница 71: ...11 DIMENSIONS GEK 98514B BUS1000 Busbar Protection 11 5 FIGURE 20 BREAKER BLOCK DIAGRAM 226B2211F23 ÿ ÿ ÿ ÿ ÿ ...
Страница 74: ...11 DIMENSIONS 11 8 BUS1000 Busbar Protection GEK 98514B FIGURE 23 CABINET 226B2211F21 ...
Страница 104: ...13 SCHEMATICS DOUBLE BUSBAR 13 16 BUS1000 Busbar Protection GEK 98514B ...
Страница 107: ...13 SCHEMATICS DOUBLE BUSBAR GEK 98514B BUS1000 Busbar Protection 13 19 16 TEST UNIT ZONES A B 226B6429F16 ...
Страница 121: ...13 SCHEMATICS DOUBLE BUSBAR GEK 98514B BUS1000 Busbar Protection 13 33 31 POWER SUPPLY AUXILIARY CIRCUITS 226B6429F31 ...
Страница 123: ...13 SCHEMATICS DOUBLE BUSBAR GEK 98514B BUS1000 Busbar Protection 13 35 43 SIGNALLING CONTACT OUTPUTS 226B6429F43 ...
Страница 124: ...13 SCHEMATICS DOUBLE BUSBAR 13 36 BUS1000 Busbar Protection GEK 98514B CABINETS INTERCONNECTIONS 226B6429F44 ...