Chapter 3. Programming
64
PanaFlow™ LC User’s Manual
Figure 70: Path Configuration
3.6.4 Programming the Flow and Diagnostic Limits
Use steps as in section “Log-in and Primary Pages” to navigate to the
Programming page
. Refer to Figure 71
for the Path configuration options.
1.
Highlight
[Composite]
and press
[ENTER]
. Scroll down and select
[Limits]
and press
[ENTER]
.
2.
Program the minimum flow velocity in
[Min Velocity]
and maximum flow velocity in
[Max Velocity]
.
3.
Program the appropriate velocity warning limits in
[Min Vel Warn Limit]
and
[Max Vel Warn Limit]
.
The values programmed in the warning limits should be tighter than those programmed in
[Min Velocity]
and
[Max Velocity]
for early warning indications on the LCD and Errors.
4.
To cutoff the near zero measurements program an appropriate value in
[Zero Cutoff]
.
d.
In order to see stable averaged flow, program the time window for which flow should be averaged in
[Flow Averaging]
. For example if a value 16 is programmed in for
[Flow Averaging]
, the flow value will
have the average of the last 16s of flow values. This allows the flow values on the display and the
outputs to be less noisy.
5.
If in section “Programming the Fluid” on page 62, Tracking was selected as
OFF
, program the
[Soundspeed Error %]
. This configuration will be used to validate if the measured sound speed is
within the programmed range of the nominal sound speed. In case the measured sound speed is
outside the
[Soundspeed Error %]
of the nominal sound speed a E2: Soundspeed Error is reported.
Figure 71: Flow and Diagnostic Limits
Programming
Composite
Prigram/Composite
Pipe
Fluid
Path
Limits
Prigram/Composite
Fluid
Channel 1
Path
Path Configuration
Channel 2
Advanced
Path Weights
Channel 3
Path
Path Configuration/Std
1 Tilted Diameter (TD)
Path Error Handling
3 Path (TD - TD - TD)
Path Weights
Channel 1
CH #1/Path Weight
Path
Limits
Path Configuration
Path Error Handling
Path Weights
2 Path (TD - TD)
CH #1/Path Weight
0.20
Channel 2
Channel 3
9
2
9
2
9
9
2
9
2
or
2
9
CH #1/Path Weight
0.20
9
Path
Path Error Handling
On
Path Configuration
Path Error Handling
Path Weights
Off
9
or
2
9
or
2
9
Operator Access or Higher
[ ]
2
9
[ ]
UNDO
MOVE
[ ]
[ ]
SAVE
ALTER
Programming
Composite
Prigram/Composite
Pipe
Fluid
Limits
Path
Prigram/Composite
Fluid
Channel 1
Limits
Max Vel Warn Limit
Channel 2
Advanced
Soundspeed Error %
Channel 3
Limits
Min Velocity
Zero Cutoff
Path
Limits
Min Velocity
Min Vel Warn Limit
Max Velocity
- 82.00
ft/s
Max Vel Warn Limit
Min Velocity
Flow Averaging
Operator Access or Higher
[ ]
2
9
[ ]
UNDO
MOVE
[ ]
[ ]
SAVE
ALTER
9
2
9
2
9
or
2
9
Min Velocity
-82.00
9
or
2
9
UNIT: ft/s
Содержание Baker Hughes PanaFlow LC XMT1000
Страница 1: ...Flow 910 327 Rev A Sep 2019 bhge com PanaFlow LC User s Manual ...
Страница 2: ......
Страница 4: ...ii no content intended for this page ...
Страница 10: ...Contents viii PanaFlow LC User s Manual ...
Страница 14: ...Preface xii PanaFlow LC User s Manual no content intended for this page ...
Страница 104: ...Chapter 4 Error Codes and Troubleshooting 90 PanaFlow LC User s Manual no content intended for this page ...
Страница 106: ...Chapter 5 Maintenance and Service 92 PanaFlow LC User s Manual no content intended for this page ...
Страница 112: ...Appendix A Specifications and Model Configurations 98 PanaFlow LC User s Manual no content intended for this page ...
Страница 139: ...PanaFlow LC User s Manual 125 Appendix D Modbus Map Appendix D Modbus Map D 1 Input Registers Map ...
Страница 142: ...Appendix E CE Mark Compliance 128 PanaFlow LC User s Manual no content intended for this page ...
Страница 180: ...Appendix H Foundation Fieldbus Communication 166 PanaFlow LC User s Manual no content intended for this page ...
Страница 182: ...Warranty 168 PanaFlow LC User s Manual no content intended for this page ...
Страница 189: ......