Chapter 3. Operation
8 | DPS 5000 Series Instruction Manual-English
© 2018 Baker Hughes, a GE company – All rights reserved.
3.7 To Change the Operation – Objects: 0x2000 – 0x2FFFF
3.7.1 0x210C– Node ID
Valid node ID can be in the range 0x01 to 0x7F. Changes to this value do not take effect unless
saved and the power cycled.
3.7.2 0x210D – Bit Rate
The bit rate at which the sensors communicate can be one of the following values:
Changes to the bit rate value does not take effect unless saved and the power cycled.
3.7.3 0x2200 – To Change the Calibration Data
To write new calibration values in objects 0x2201 to 0x220A, set object 0x2200 (Calibration
Access Pin) to 4118.
To prevent accidental changes to the calibration data, set the value to 0 after completing all
the changes.
3.7.4 0x2201 to 0x2203 – The Last Calibration Year, Month, Day
Refer to “0x2200 – To Change the Calibration Data” on page 8. The initial values identify the
date of the factory calibration. After each calibration, set a new date (refer to Chapter 4.,
“Maintenance,” on page 15).
3.7.5 0x2204 to 0x2206 – The Next Calibration Year, Month, Day
Refer to “0x2200 – To Change the Calibration Data” on page 8. The initial values identify the
date of the factory calib one year. After each calibration, set a new date (refer to
Chapter 4., “Maintenance,” on page 15).
Value
Baud Rate
10
10 kbit/s
20
20 kbit/s
50
50 kbit/s
125
125 kbit/s
250
250 kbit/s
500
500 kbit/s
800
800 kbit/s
1000
1000 kbit/s