CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE
3-111
3
3.5.2.77 Trip output (TrOut)
This element is instantiated in the following products: C60, D60, L60, L90.
Table 3-126: Trip output data objects
dirGeneral
ENUMERATED
ST
0, the code for unknown
R
InRef
αα
ORG
TRIP BUS # INPUT
α
setting.
R
setSrcRef
ObjectReference SP TRIP BUS # INPUT
α
setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef99
ORG
TRIP BUS # RESET setting, which when On
resets the non-volatile set-dominant
input conditions latch.
R
setSrcRef
ObjectReference SP TRIP BUS # RESET setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
BlkRef1
ORG
TRIP BUS # BLOCK setting.
R
setSrcRef
ObjectReference SP TRIP BUS # BLOCK.
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
LNName: TrOutPTRC1
LDevice inst: Prot
UR element: Trip Output element
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Tr
ACT
TRIP OUTPUT OP (any trip) operand
R
general
BOOLEAN
ST TRIP OUTPUT OP
R
Tr3p
ACT
TRIP 3-POLE operand
R
general
BOOLEAN
ST TRIP 3-POLE
R
Tr1p
ACT
general is TRIP 1-POLE operand, phsA is
TRIP PHASE A operand, phsB is TRIP
PHASE B operand and phsC is TRIP PHASE
C operand
R
general
BOOLEAN
ST TRIP 1-POLE
R
phsA
BOOLEAN
ST TRIP PHASE A
R
phsB
BOOLEAN
ST TRIP PHASE B
R
phsC
BOOLEAN
ST TRIP PHASE C
R
StrRec3p
SPS
TRIP AR INIT 3-POLE operand
R
stVal
BOOLEAN
ST TRIP AR INIT 3-POLE
R
Tr3pFrcd
SPS
TRIP FORCE 3-POLE operand (3-pole trip
mode is being forced)
R
stVal
BOOLEAN
ST TRIP FORCE 3-POLE
R
StrZ2PhDl
SPS
TRIP Z2PH TMR INIT operand
R
stVal
BOOLEAN
ST TRIP Z2PH TMR INIT
R
StrZ2GndDl
SPS
TRIP Z2GR TMR INIT operand
R
stVal
BOOLEAN
ST TRIP Z2GR TMR INIT
R
InRef3
α
ORG
TRIP 3-POLE INPUT-
α
setting.
R
setSrcRef
ObjectReference SP TRIP 3-POLE INPUT-
α
setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef1
α
ORG
TRIP 1-POLE INPUT-
α
setting.
R
setSrcRef
ObjectReference SP TRIP 1-POLE INPUT-
α
setting
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef2
α
ORG
TRIP RECLOSE INPUT-
α
setting.
R
setSrcRef
ObjectReference SP TRIP RECLOSE INPUT-
α
setting reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
InRef01
ORG
START TMR Z2PH Inp1 setting.
R
setSrcRef
ObjectReference SP START TMR Z2PH Inp1 setting
reference to the data attribute to input
R/C
LNName: TrBusPTRC#
LDevice inst: Prot
UR element: Trip Bus element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C