3-48
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-32: C70 capacitor bank phase overvoltage function data objects
LNName: CPhOvPTOV#
LDevice inst: Prot
UR element: BANK OVERVOLTAGE element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
BANK OV # PKP operands (including
individual three phases), which indicates
element will operate when delay expires.
R
general
BOOLEAN
ST BANK OV # PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element is non-directional
R
phsA
BOOLEAN
ST BANK OV # PKP A
R
dirPhsA
ENUMERATED
ST
0, the code for unknown.
R
phsB
BOOLEAN
ST BANK OV # PKP B
R
dirPhsB
ENUMERATED
ST
0, the code for unknown.
R
phsC
BOOLEAN
ST BANK OV # PKP C
R
dirPhsC
ENUMERATED
ST
0, the code for unknown.
R
Op
ACT
BANK OV # OP operands (including
individual three phases)
R
general
BOOLEAN
ST BANK OV # OP
R
phsA
BOOLEAN
ST BANK OV # OP A
R
phsB
BOOLEAN
ST BANK OV # OP B
R
phsC
BOOLEAN
ST BANK OV # OP C
R
Dpo
SPS
BANK OV # DPO operand
R
stVal
BOOLEAN
ST BANK OV # DPO
R
BlkRef
γ
ORG
BANK OV # BLK setting for setting group
γ
.
R
setSrcRef
ObjectReference SP BANK OV # BLK for group
γ
.
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
OpV
WYE
Bank Operating Voltage in per unit for Ph
A, B, and C
R
phsA
CMV
R
phsA.instCVal
Vector
MX
R
phsA.instCVal.mag
.f
FLOAT32
Bank overvoltage # phase A
operate voltage
R
phsA.cVal
Vector
MX
R
phsA.cVal.mag.f
FLOAT32
instCVal.mag.f deadbanded
R
phsA.units
Unit
CF
R
phsA.units.SIUnit ENUMERATED
1, the code for dimensionless (per unit)
R
phsA.units
.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
phsA.db
INT32U
CF CPhOvPTOV#.OpV.phsAdb
R/W/C
phsA.zeroDb
INT32U
CF (VOLTAGE CUT-OFF LEVEL) / 275 *
100 000
R
phsB
CMV
R
phsB.instCVal
Vector
MX
R
phsB.instCVal.mag
.f
FLOAT32
Bank overvoltage # phase B
operate voltage
R
phsB.cVal
Vector
MX
R
phsB.cVal.mag.f
FLOAT32
instCVal.mag.f deadbanded
R
phsB.units
Unit
CF
R
phsB.units.SIUnit ENUMERATED
1, the code for dimensionless (per unit)
R
phsB.units
.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
phsB.db
INT32U
CF CPhOvPTOV#.OpV.phsB.db
R/W/C
phsB.zeroDb
INT32U
CF (VOLTAGE CUT-OFF LEVEL) / 275 *
100 000
R
phsC
CMV
R
phsC.instCVal
Vector
MX
R
phsC.instCVal.mag
.f
FLOAT32
Bank overvoltage # phase B
operate voltage
R