CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE
3-95
3
3.5.2.59 Phase overvoltage (PhsOv)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60,
T60.
Table 3-104: Phase overvoltage data objects
3.5.2.60 Phase select (PhSel)
This element is instantiated in the following products: C60, D60, L60, L90.
Table 3-105: Phase select data objects
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
LNName: PhsOvPTOV#
LDevice inst: Prot
UR element: Phase Overvoltage element # functions
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
PHASE OV # PKP operands (including
individual three phases)
R
general
BOOLEAN
ST PHASE OV # PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element is non-directional
R
phsA
BOOLEAN
ST PHASE OV # PKP A
R
dirPhsA
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element is non-directional
R
phsB
BOOLEAN
ST PHASE OV # PKP B
R
dirPhsB
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element is non-directional
R
phsC
BOOLEAN
ST PHASE OV # PKP C
R
dirPhsC
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element is non-directional
R
Op
ACT
PHASE OV # OP operand (including
individual three phases)
R
general
BOOLEAN
ST PHASE OV # OP
R
phsA
BOOLEAN
ST PHASE OV # OP A
R
phsB
BOOLEAN
ST PHASE OV # OP B
R
phsC
BOOLEAN
ST PHASE OV # OP C
R
Dpo
SPS
PHASE OV # DPO operand, which is the
inverse of PHASE OV PKP
R
stVal
BOOLEAN
ST PHASE OV # DPO
R
DpoPhs
β
SPS
PHASE OV# DPO
β
operand” (where
β
refers to Phase-A, B or C)
R
stVal
BOOLEAN
ST PHASE OV# DPO
β
(where
β
refers to Phase-A, B or C)
R
BlkRef
γ
ORG
PHASE OV # BLK setting for setting group
γ
.
R
setSrcRef
ObjectReference SP PHASE OV # BLK for group
γ
.
reference to the data attribute to input
R/C
setSrcCB
ObjectReference SP
source GoCB of input if via GOOSE
R/C
LNName: PhSelGAPC1
LDevice inst: Prot
UR element: Phase select element
data obj. data attribute
Type
FC UR Name
Description
R/W/C
FltAG
SPS
PHASE SELECT AG operand
R
stVal
BOOLEAN
ST PHASE SELECT AG
R
FltBG
SPS
PHASE SELECT BG operand
R
stVal
BOOLEAN
ST PHASE SELECT BG
R
FltCG
SPS
PHASE SELECT CG operand
R
stVal
BOOLEAN
ST PHASE SELECT CG
R
FltSLG
SPS
PHASE SELECT SLG operand
R
LNName: PhsIocPIOC#
LDevice inst: Prot
UR element: Phase Instantaneous Overcurrent element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C