Table 4-5. Specifications for IC693PWR330 High Capacity AC/DC Input Power Supply
Nominal Rated Voltage
Input Voltage Range
AC
DC
20/240 VAC or
25 VDC
85 to 264 VAC
00 to 300 VDC
Input Power
(Maximum with Full Load)
00 VA with VAC Input
50 W with VDC Input
Inrush Current
4A peak, 250 ms maximum
Output Power
5 VDC:
30 watts maximum
24 VDC Relay:
5 watts maximum
24 VDC Isolated:
20 watts maximum
NOTE:
30 watts maximum total (all three outputs)
Output Voltage
5 VDC:
5.0 VDC to 5.2 VDC (5.
VDC nominal)
24 VDC Relay:
24 to 28 VDC
24 VDC Isolated:
2
.5 VDC to 28 VDC
Protective Limits
Overvoltage:
Overcurrent:
5 VDC output:
6.4 to 7 V
5 VDC output:
7 A maximum
Holdup Time:
20 ms minimum
Field Wiring Connections for the AC/DC Input Power Supplies
The two AC/DC input power supplies have six terminals for user connections. These connections
are described below.
AC Power Source Connections
The Hot, Neutral, and Ground wires from the
20 VAC power source or L
, L2, and
Ground wires from the 240 VAC power source connect to the system through the top three
terminals of the terminal strip on the front of the power supply.
DC Power Source Connections
Connect the
+
and
-
wires from the
25 VDC (nominal) power source to the top two
terminals on the terminal connector. These connections are not polarity-sensitive on an
AC/DC input power supply. (However, the DC Input-only type supplies, which are
discussed later in this chapter, are polarity sensitive.)
Input Overvoltage Protection Devices
This information applies to all Series 90-30 power supplies except IC693PWR322
and IC693PWR328.
The overvoltage protection devices for this power supply are
connected internally to pin 4 on the user terminal strip. This pin is normally connected to
frame ground (pin 3) with the supplied jumper strap which is installed at the factory. If
overvoltage protection is not required
or
is supplied upstream, this feature can be disabled
by removing the jumper strap from pins 3 and 4.