3-6
Series 90-30 PLC Installation and Hardware Manual
–
August 2002
GFK-0356Q
3
Modular CPU Baseplates (Figures 3-4 and 3-5)
Ŷ
A Power Supply module must be plugged into the left slot (which is not numbered) of these
baseplates. The left slot is a unique size and type that only supports a Power Supply module.
Ŷ
A CPU module (or a special Option module) must be installed in Slot 1 of these baseplates.
Slot 1 is a unique size and type that only supports a CPU module or a special Option module
like the FIP Remote I/O Scanner (IC693BEM330). Slot 1 is labeled CPU/1.
Ŷ
Slots numbered 2 and above are of a unique size and type that only supports I/O or Option
modules.
Ŷ
Expansion and Remote baseplates are supported, so a 25-pin D-type female expansion
connector is located at the right end of the baseplate for connecting to an Expansion or Remote
baseplate.
Ŷ
Since the CPU is modular, it can be replaced or changed to a different type if additional
features are desired.
Ŷ
Only one CPU baseplate is allowed per system. If more than one baseplate is used in a system,
the additional ones must be either Expansion or Remote types.
Ŷ
A modular CPU baseplate is always assigned, by default, Rack Number 0.
I/O-2
I/O-3
I/O-4
I/O-5
C
P
U
PROGRAMMABLE
CONTROLLER
BASE 5-SLOT
CAUTION
USER PROGRAM
AND REGISTER
VALUES MAY BE
LOST IF POWER
SUPPLY IS
REMOVED FOR
LONGER THAN
1 HOUR
POWER
SUPPLY
NON-CPU SLOTS
E
X
P
A
N
S
I
O
N
CPU/1
Figure 3-4. IC693CHS397 5-Slot Modular CPU Baseplate
PROGRAMMABLE
CONTROLLER
BASE 10-SLOT
I/O-2
I/O-3
I/O-4
I/O-5
I/O-6
I/O-7
I/O-8
I/O-9
I/O-10
CPU/1
POWER
SUPPLY
NON-CPU SLOTS
NON-CPU SLOTS
C
P
U
E
X
P
A
N
S
I
O
N
USER PROGRAM
AND REGISTER
VALUES MAY BE
LOST IF POWER
SUPPLY IS
REMOVED FOR
LONGER THAN
1 HOUR
CAUTION
Figure 3-5. IC693CHS391 10-Slot Modular CPU Baseplate