Programmer Hardware Products
GFK-0356Q
Chapter 11 Programmer Hardware Products
11-5
11
IC693PRG300 Hand-Held Programmer (HHP)
Some models of the Series 90-30 PLC can be programmed with the GE Hand-Held
Programmer (HHP). The HHP uses the Statement List Language. With the HHP, you can develop,
debug, and monitor logic programs, monitor data tables, and configure PLC and I/O parameters.
Note
The user logic program in Series 90-30 CPU numbers 350 and above cannot be
viewed or edited with the Hand-Held Programmer. You must use
Logicmaster 90-30, Control, VersaPro, or Logic Developer-PLC programming
software with those CPUs.
The HHP connects to the CPU serial port through a 15-pin D-type connector on the Series 90-30
PLC power supply in the CPU baseplate. The physical connection is through a 6-foot (2-meters)
long cable (IC693CBL303). This cable also provides power connections to the HHP, and provides
a signal that tells the PLC that an HHP is attached. The HHP can be connected or disconnected
while the PLC is powered-up. The HHP does not require communications parameter configuration
in order to communicate with a PLC. This makes it useful for troubleshooting a communications
problem between a PC and the PLC.
AQ
UPCTR
DNCTR
ENT
TMR
ONDTR
RSTM
RST
SETM
SET
LD
MODE
OUT
OUTM
AND
D
OR
E
NOT
F
BLK
RUN
I
A I
A
Q
B
M
T
C
G
S
FUNC
DEL
7
8
9
R
4
5
6
1
2
3
0
WRITE
#
CLR
READ
VRFY
SRCH
INS
HEX
DEC
SERIES 90-30
PROGRAMMABLE
CONTROLLER
HAND HELD PROGRAMMER
a43052
SERIAL PORT CONNECTOR
TO CPU SERIAL PORT
SLOT
FOR
MEMORY
CARD
Figure 11-5. Hand-Held Programmer for the Series 90-30 PLC