![GE 90-30 PLC Скачать руководство пользователя страница 134](http://html.mh-extra.com/html/ge/90-30-plc/90-30-plc_installation-and-hardware-manual_122953134.webp)
GFK-0356Q
Chapter 5 CPUs
5-23
5
CPU364 Hardware Features
This module has four LED indicator lights, an Ethernet Restart pushbutton, a standard CPU
keyswitch, three port connectors, and a shield ground connection tab (labeled “FRAME”).
CPU 364
PS
PORT
RS-232
PORT 1
AAUI
EOK
LAN
FRAME
STAT
ETHERNET
RESTART
10BASE T
ON
OFF
PIN 1
LED Indicators
There are four LED Indicators. Three relate to the Ethernet interface: EOK, LAN, and STAT.
These can be ON, OFF, FLASHING slow, or FLASHING fast in several different combinations.
The full functionality of these LEDs is detailed in GFK-1541,
TCP/IP Ethernet Communications
for the Series 90 PLC User’s Manual.
The fourth LED, PS PORT, is for the CPU’s serial port and is not related to the Ethernet interface.
This LED will flash while data is being transferred through the SNP serial port connector on the
PLC power supply, and will stay off when the port is inactive. (On some early production 364
CPUs, this LED is labeled “SNP.”) All Series 90-30 CPUs have this standard serial port.
Ethernet Restart Pushbutton
This pushbutton performs four functions: LED test, Restart, Restart and enter Software Load state,
and Restart and enter Maintenance state. These are detailed in GFK-1541,
TCP/IP Ethernet
Communications for the Series 90 PLC User’s Manual.