369 MOTOR MANAGEMENT RELAY – QUICKSTART GUIDE
SPECIFICATIONS CHAPTER 5: PRODUCT DESCRIPTION
5.2.4
Communications
FRONT PORT
Type: .....................................................................RS232, non-isolated
Baud rate: ..........................................................4800 to 19200
Protocol:..............................................................Modbus
®
RTU
BACK PORTS (3)
Type: .....................................................................RS485
Baud rate: ..........................................................1200 to 19200
Protocol:..............................................................Modbus
®
RTU
36V isolation (together)
PROFIBUS (OPTIONS P AND P1)
Type: .....................................................................RS485
Baud rate: ..........................................................1200 baud to 12 Mbaud
Protocol:..............................................................Profibus-DP
Profibus-DPV1
Connector Type:..............................................DB9 Female
MODBUS/TCP ETHERNET (OPTION E)
Connector type:...............................................RJ45
Protocol:..............................................................Modbus/TCP
DEVICENET (OPTION D)
DeviceNet CONFORMANCE TESTED™
Connector type:...............................................5-pin linear DeviceNet plug (phoenix type)
Baud rate: ..........................................................125, 250, and 500 kbps
Protocol:..............................................................DeviceNet
Bus-Side Current Draw:...............................85mA (Typical), 100mA (Max)
FIBER OPTIC PORT (OPTION F)
Optional use:.....................................................RTD remote module hookup
Baud rate: ..........................................................1200 to 19200
Protocol:..............................................................Modbus
®
RTU
Fiber sizes: .........................................................50/125, 62.5/125, 100/140, and 200
μ
m
Emitter fiber type: ..........................................820 nm LED, multimode
Link power budget:
Transmit power: ...........................................–20 dBm
Received sensitivity: ...................................–30 dBm
Power budget: ...............................................10 dB
Maximum optical input power: ...............–7.6 dBm
Typical link distance: ....................................1.65 km
Note
Typical link distance is based upon the following assumptions for system loss. As actual
losses vary between installations, the distance covered will vary.
Connector loss: ...............................................2 dB
Fiber loss: ..........................................................3 dB/km
Splice loss: ........................................................One splice every 2 km at 0.05 dB loss/splice
System margin: ..............................................3 dB additional loss added to calculations to compensate
for all other losses