CHAPTER 4: KEYPAD SETPOINTS
S10 ANALOG OUTPUTS
369 MOTOR MANAGEMENT RELAY – QUICKSTART GUIDE
4–53
4.8
S10 Analog Outputs
4.8.1
Analog Outputs
PATH: S10 ANALOG OUTPUTS
Ø
ANALOG OUTPUT 1(4)
The analog output parameters are indicated in the following table:
ANALOG OUTPUT 1
ANALOG OUTPUT 1:
DISABLED
Range: Disabled, Enabled
ANALOG OUTPUT 1
RANGE: 0-1 mA
Range: 0–1mA, 0–20 mA, 4–20 mA
ANALOG OUTPUT 1:
Phase A Current
Range: See Analog Output selection table
ANALOG OUTPUT 1
MIN: 0 A
Range: See Analog Output selection table
ANALOG OUTPUT 1
MAX: 100 A
Range: See Analog Output selection table
Table 4–2: Analog Output Parameters
PARAMETER NAME
RANGE /UNITS
STEP
DEFAULT
MINIMUM
MAXIMUM
Phase A Current
0 to 65535 A
1
0
100
Phase B Current
0 to 65535 A
1
0
100
Phase C Current
0 to 65535 A
1
0
100
Avg. Phase Current
0 to 65535 A
1
0
100
AB Line Voltage
0 to 65000 V
1
3200
4500
BC Line Voltage
0 to 65000 V
1
3200
4500
CA Line Voltage
0 to 65000 V
1
3200
4500
Avg. Line Voltage
0 to 65000 V
1
3200
4500
Phase AN Voltage
0 to 65000 V
1
1900
2500
Phase BN Voltage
0 to 65000 V
1
1900
2500
Phase CN Voltage
0 to 65000 V
1
1900
2500
Avg. Phase Voltage
0 to 65000 V
1
1900
2500
Hottest Stator RTD
–40 to +200°C
or
–40 to +392°F
1
0
200
RTD #1 to 12
–40 to +200°C
or
–40 to +392°F
1
–40
200
Power Factor
–0.99 to 1.00
0.01
0.01
0.80