CHAPTER 5: PRODUCT DESCRIPTION SPECIFICATIONS
369 MOTOR MANAGEMENT RELAY – QUICKSTART GUIDE
5–63
Explosion Hazard – Substitution of components may impair suitability for Class 1, Div 2.
Explosion Hazard – Do not disconnect equipment unless power has been switched off
or the area is known to be Non-Hazardous.
5.2.3
Metering
POWER METERING (OPTION M)
EVENT RECORD
Capacity:.............................................................last 512 events
Triggers:..............................................................trip, inhibit, power fail, alarms, self test,
waveform capture
WAVEFORM CAPTURE
Length: ................................................................3 buffers containing 16 cycles of all current and voltage
channels
Trigger position: ..............................................1 to 100% pre-trip to post-trip
Trigger: ...............................................................trip, manually via communications or digital input
MOTOR START DATA LOGGER
Length: ...............................................................6 Buffers containing 30 seconds of motor start data.
Trigger: ...............................................................Motor Start Status.
Trigger position: .............................................1-second pre-trigger duration.
Logging rate: ...................................................1 sample/200ms.
PARAMETER ACCURACY
(FULL SCALE)
RESOLUTION
RANGE
kW
±
2%
1 kW
±32000
kvar
±
2%
1 kvar
±
32000
kVA
±
2%
1 kVA
0 to 65000
kWh
±
2%
1 kWh
0 to 999
MWh
±2%
1 MWh
0 to 65535
±
kvarh
±
2%
1 kvarh
0
to 999
±Mvarh
±2%
1 Mvarh
0 to 65535
Power Factor
±
1%
0.01
–0.99 to 1.00
Frequency
±
0.02 Hz
0.01 Hz
20.00 to
100.00
kW Demand
±
2%
1 kW
0 to 32000
kvar Demand
±
2%
1 kvar
0 to 32000
kVA Demand
±
2%
1 kVA
0 to 65000
Amp Demand
±
2%
1 A
0 to 65535