FASD700 aspirated smoke detector – Installation manual
12
3.3.2 FASD715 / FASD717 functions
Access the required funtion as described in section 3.1 Selecting and programming
functions. The relevant LED will flash continuously to indicate the active function.
Table 2: FASD715 / FASD717 functions
Function
Calibration mode
1
Code entry. See section 3.1.1 Code entry. The Code entry LED
flashes.
2
To RESET the panel press SELECT when the Reset LED is
flashing.
3
Select Isolate channel. The Isolate LEDs flash (constant illumination
when set).
4
Set fan speed. The Power LED flashes.
5
Set sensitivity of bar graph to changes in airflow velocity. The Flow
OK LED flashes.
6
Select the bar graph LED segment
above
which the Flow HI LED
will be illuminated. The Flow HI LED flashes.
7
Select the bar graph LED segment
below
which the Flow LO LED
will be illuminated. The Flow LO LED flashes.
8
Set smoke detector ALERT alarm threshold. The Alert LED flashes.
9
Set smoke detector ACTION alarm threshold. The Action LED
flashes.
10
Set smoke detector FIRE alarm threshold. The Fire LED flashes.
11
Select Mains/Battery fault detection. The general Fault LED flashes
(Mains / Battery LED flashes if selected)
12
Calibrate flow sensors at zero and selected airflow speed. The Fan
fault LED flashes (Fan and Power LEDs flash during calibration).
13
Exit function selection and return to normal mode. A 20 second time-
out function will also exit calibration mode. Smoke detector level
displayed as cumulative bar graph on each display.
3.3.3 Unit alarms
CH1 FIRE; CH1 ACTION; CH2 FIRE; CH2 ACTION (4 relays).
CH1 smoke detector, airflow or power Fault (1 relay).
CH2 smoke detector, airflow or power Fault (1 relay).