background image

D200-14-00 

I56-0084-009R

DH100ACDCLP Air Duct Smoke Detector  
with Extended Air Speed Range

INSTALLATION AND MAINTENANCE INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

The Innovair DH100ACDCLP model is a photoelectric detector ap-
proved for an extended air speed range of 

100 to 4000 feet per 

minute

  (0.5  m/s  to  20.3  m/s)  and  an  operational  temperature 

range of 32°F to 131°F (0°C to 55°C).

Before Installing

Please thoroughly read the System Sensor Guide for Proper Use 
of  Smoke  Detectors  in  Duct  Applications  (A05-1004),  which 
provides  detailed  information  on  detector  spacing,  placement, 
zoning, wiring, and special applications. Copies of this manual 
are  available  online  at  www.systemsensor.com  or  via  System 
Sensor’s  toll  free  fax-back  service,  Documents  on  Demand  at 
800/736-7672. NFPA Standards 72 and 90A should also be refer-
enced for detailed information. 

NOTICE:

  This  manual  shall  be  left  with  the  owner/user  of 

this equipment.

IMPORTANT:

  This  detector  must  be  tested  and  maintained  reg-

ularly  following  NFPA  72  requirements.  The  detector  should  be 
cleaned at least once a year.

Table of Contents 

Page

[1] General Description  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
[2] Limitations of Duct Smoke Detectors . . . . . . . . . . . . . . . . . 1
[3] Contents of the Duct Smoke Detector Kit . . . . . . . . . . . . . . 1
[4] Exploded View of Duct Smoke Detector Components . . . . . . . 2
[5] Installation Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
[6] Duct Smoke Detector Maintenance & Test Procedures . . . . . . . 4
[7] Detector Cleaning Procedures . . . . . . . . . . . . . . . . . . . . . . 7
[8] Board Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
[9] Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Warranty   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

[1] General Description

An HVAC system supplies conditioned air to virtually every area 
of a building. Smoke introduced into this air duct system will be 
distributed  throughout  the  entire  building.  Smoke  detectors  de-
signed for use in air duct systems are used to sense the presence 
of smoke in the duct. 
Model DH100ACDCLP Air Duct Smoke Detector utilizes photoelec-
tric technology for the detection of smoke. This detection method, 
when  combined  with  an  efficient  housing  design,  samples  air 
passing  through  the  duct  and  allows  detection  of  a  developing 
hazardous condition. When sufficient smoke is sensed, an alarm 
signal is initiated and appropriate action can be taken to shut off 
fans,  blowers,  change  over  air  handling  systems,  etc.  These  ac-
tions can facilitate the management of toxic smoke and fire gases 
throughout the areas served by the duct system.
The DH100ACDCLP detector is designed to operate on 24 VDC/
VAC, 120 VAC, or 240 VAC. Alarm and supervisory relay con-
tacts are available for control panel interface (alarm initiation), 
HVAC  control,  and  other  auxiliary  functions.  Auxiliary  relays 
are  also  provided  for  fan  shut  down  or  signaling  of  up  to  9 
other detectors in the loop for multiple fan shut down. These 
detectors are not designed for 2-wire applications.

For testing, the alarm can be enabled by a magnet activated test 
switch or by the optional remote test station. The duct smoke 
detector latches into alarm state when an alarm occurs. A green 
LED  flashes  to  indicate  power,  a  red  LED  signals  local  alarm 
indication, and optional accessories offer a variety of annuncia-
tion capabilities.
The  DH100ACDCLP  can  be  reset  by  a  momentary  power  inter-
ruption, the reset button on the front cover, the control panel, or 
remote reset accessory. 

The DH100ACDCLP incorporates a cover 

tamper feature that provides a trouble signal after 7 minutes if 
the cover is removed or improperly installed.

 Proper installation 

of the cover removes the trouble condition.

[2] Limitations Of Duct Smoke Detectors 

WARNING

The  National  Fire  Protection  Association  has  established  that 
DUCT DETECTORS MUST NOT BE USED AS A SUBSTITUTE FOR 
OPEN AREA DETECTOR PROTECTION as a means of providing 
life safety. Nor are they a substitute for early warning in a build-
ing’s regular fire detection system.

System  Sensor  supports  this  position  and  strongly  recom-
mends that the user read NFPA Standards 90A, 72, and 101. The 
DH100ACDCLP Air Duct Smoke Detectors are listed per UL 268A.

This device will not operate without electrical power. Fire situa-
tions may cause an interruption of power. The system safeguards 
should be discussed with your local fire protection specialist.

This device will not sense smoke unless the ventilation system is 
operating and the cover is installed.

For this detector to function properly, it MUST be installed accord-
ing to the instructions in this manual. Furthermore, the detector 
MUST be operated within ALL electrical and environmental speci-
fications  listed  in  this  manual.  Failure  to  comply  with  these  re-
quirements may prevent the detector from activating when smoke 
is present in the air duct.

[3] Contents Of The Duct Smoke Detector Kit

1.  Complete housing base and cover assembly
2.  Two #10 x 1

1

/

4

˝ sheet metal screws for mounting

3.  Two sampling tube filters
4.  One test magnet
5.  Drilling template
6.  Two foam gaskets
7.   Four #6-self tapping mounting screws for the metal sampling 

tube and optional exhaust tube extension

8.  One sampling tube end cap
9.  One plastic sampling tube
10.  One #8 self-tapping screw for the plastic sampling tube

NOTE:

  For  ducts  over  1

1

2

  feet,  longer  sampling  tubes  must  be 

ordered  to  complete  the  installation.  They  must  be  the  correct 
length for the width of the duct where they will be installed. See 
Table 1 on page 3 to determine the inlet tube required for different 
duct widths. 

I56-0084-009R

Summary of Contents for DH100ACDCLP

Page 1: ...ry functions Auxiliary relays are also provided for fan shut down or signaling of up to 9 other detectors in the loop for multiple fan shut down These detectors are not designed for 2 wire applications For testing the alarm can be enabled by a magnet activated test switch or by the optional remote test station The duct smoke detector latches into alarm state when an alarm occurs A green LED flashe...

Page 2: ... in Figure 3 Use the two 11 4 long sheet metal screws to screw the detector housing to the duct CAUTION Do not overtighten the screws Figure 3 Installation of foam gaskets over sampling tube bushings SCREW HOLES FOR ATTACHING HOUSING TO DUCT WORK H0107 00 5 4 Sampling Tube Installation for Ducts Greater Than 11 2 Feet Wide The sampling tube is identified by a series of air inlet holes on the tube ...

Page 3: ...ng holes so that there are a total of 10 to 12 holes spaced as evenly as possible across the width of the duct NOTE Air currents inside the duct may cause excessive vibra tion especially when the longer sampling tubes are used In these cases a 3 floor flange available at most plumbing supply stores may be used to fasten the sampling tube to the other side of the duct When using the flange connecto...

Page 4: ...an 18 gauge The duct smoke detector terminals accommodate wire sizes up to 12 gauge Smoke detectors and alarm system control panels have specifi cations for allowable loop resistance Consult the control panel manufacturer s specifications for the total loop resistance allowed for the particular model control panel being used before wiring the detector loop Wiring Instructions The DH100ACDCLP detec...

Page 5: ...ntial fall below 0 0015 inches of water 6 2 Standby Alarm and Sensitivity Tests The cover must be removed to perform these tests The use of a remote accessory for visible indication of power and alarm is recommended 6 2 1 Standby And Trouble Standby Look for the presence of the flashing green LED The LED should flash approximately ev ery 10 seconds Trouble If the detector LED does not flash then t...

Page 6: ...LE POWER INPUTS ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN ETC 16 6 17 7 18 8 N C C N O N O C N C ALARM AUXILIARY CONTACTS SHOWN IN STANDBY CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS SUPERVISORY TROUBLE CONTACTS TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS REMOVED OR WHEN TAMPER FEATURE TIMES OUT OPEN CONTACTS SIGNAL TROUBLE CONDITION TO P...

Page 7: ...er in the same fashion Vacuum the screen and cover Use clean compressed air to loosen and blow out any remaining debris Replacement screens S08 39 01 are available 3 Vacuum photo chamber then use clean compressed air to blow area clean 4 Replace the chamber by pressing it onto the base Press the screen into place It should fit tightly on the chamber 8 0 Board Replacement 8 1 Detector Board Replace...

Page 8: ...AC 50 60 Hz 120 VAC 50 60 Hz 220 240 VAC 50 60 Hz CURRENT REQUIREMENTS USING NO ACCESSORIES Max standby current 15 mA 35 mA RMS 25 mA RMS 15 mA RMS Max alarm current 70 mA 125 mA RMS 35 mA RMS 25 mA RMS CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm auxiliary contacts DPDT 10A 30 VDC 10A 250 VAC 1 4 HP 240 VAC 1 8 HP 120 VAC Trouble contacts SPDT 2 0A 30 VDC resistive 2...

Reviews: