FASD700 aspirated smoke detectors – Installation manual
Note:
For detector connection details and for alarm / end-of-line resistor values refer to the
detector / fire panel manual.
In the event of a fault on the FASD710 / FASD712 panel, the relay on the main PCB
will open the fault monitor line "DET1". This will give the fault signal on the fire panel.
2.3 Panel installation
The panel should be secured to a suitable surface using the 4 corner fixing points.
2.4 Pipe installation
For pipe installation guidelines refer to the FHSD700 Ducts Installation
manual.
Note the following:
ABS, UPVC, copper or stainless steel pipe may be used.
Pipe with an outer diameter of 25 mm or 26.7 mm may be used. An adapter is
required for used with 25 mm pipe.
Pipe lengths are cut as required and joined by sockets (permanent), solvent welded
or socket unions (removable).
Smoke tests should be performed before planning and installing the pipe network.
CAUTION!
Do not use T-joints in low-pressure wide-bore systems. These
make pipe design and air-flow calculation difficult to predict accurately.
2.5 External connections
The panels allow the following external connections.
2.5.1 FASD710 / FASD712 panels
Mains supply
24 VDC
External loop disconnect alarm relay (optional)
I/O module (optional)
2.5.2 FASD715 / FASD717 panels
Mains supply
24 VDC
Alarm relays
RS232
Isolate
External loop disconnect alarm relay (optional)
I/O module (optional)
WWW.UKPANELS.COM