![GE Security 1200C Скачать руководство пользователя страница 38](http://html.mh-extra.com/html/ge-security/1200c/1200c_installation-manual_572048038.webp)
34
1200C-2000C Fire Alarm Control Panel, Repeater, and Black Box Installation Manual
Supplementary electrical information
FR1200C-2000C
FP1200C-2000C
I min
250 mA
250 mA
I max. a
1 A
1 A
I max. b
3.5 A
4 A
Ri max
0.5
Ω
0.5
Ω
Battery voltage (final)
21 V
21 V
Battery voltage (fully charged)
27.3 V at 20ºC (36mV/ºC)
27.3 V at 20ºC (36mV/ºC)
Batteries
7 Ah to 26 Ah
7 Ah to 45 Ah
Battery capacity calculation
Battery capacity is calculated with the following formula:
C = (Standby current
×
Standby time) + (Alarm current
×
Alarm time)
Calculation example for 24 hours standby time and 30 minutes in alarm:
System data:
• 1 x zone module
• 250 mA at FEP2000N auxiliary output
• 1 x internal printer (not supplied)
• No
modem
• 2 x loops with 100 devices per loop
• 100 mA at SD2000 sounders output
Status System Aux. Printer Modem
Loops*
Sounders Total
Standby 200 mA
0.25 A 100 mA 0
340
μ
A
×
100
×
2
= 68 mA
0 618
mA
Alarm
200 mA +
100 mA =
300 mA
0.25 A 100 mA 0
340
μ
A
×
100
×
2
+ (80 mA
×
2) =
228 mA
100 mA
978 mA
C = (0.618 A
×
24 Hrs) + (0.978 A
×
0.5 Hrs) = 15.312 Ah.
Closest value is 18 Ah.
Содержание 1200C
Страница 47: ...1200C 2000C Fire Alarm Control Panel Repeater and Black Box Installation Manual 43 ...
Страница 48: ......