32
1200C-2000C Fire Alarm Control Panel, Repeater, and Black Box Installation Manual
Technical specifications
Mechanical and environmental specifications
Dimensions (W x H x D
Small
cabinet
Large
cabinet
445 x 445 x 120 mm
810 x 445 x 120 mm
Colour
RAL9016 Traffic White
IP rating
IP54
Operating temperature
−
5°C to +40°C
Storage temperature
−
20°C to +60°C
Loop specifications (2000 protocol)
Maximum number of loops per panel
See “Appendix C: Maximum zones and loops” on
page 38
Loop overload current
> 500 mA
Loop operating load
Max. 100 mA
Maximum number of addressable devices per
loop
128 per 2 km of cable
Maximum number of addressable devices per
panel including I/O devices, detectors and manual
call points
1024
Maximum number of addressable detectors
and/or manual call points per panel
512 (as defined by EN 54-2)
Loop specifications (900 protocol)
Maximum number of loops per panel
See “Appendix C: Maximum zones and loops” on
page 38
Loop overload current
> 500 mA
Loop operating load
Max. 100 mA
Maximum number of addressable devices per
loop
126 per 2 km of cable
Maximum number of addressable devices per
panel including I/O devices, detectors and manual
call points
1008
Maximum number of addressable detectors
and/or manual call points per panel
512 (as defined by EN 54-2)
Input and output specifications (SD2000/FEP2000N)
SD2000 IN1 to IN4
3K3
Ω
termination
SD2000 OUT1 and OUT2 (loop Class A)
24 V / 0.8 A (max. supervision 5V)
SD2000 OUT3 and OUT4 (loop Class A)
24 V / 0.1 A (max. supervision 5V)*
SD2000 OUT1 to OUT4 (loop Class B)
3K3
Ω
/ 680
Ω
switched output
SD2000 OUT5 to OUT8 max. switching current
2A at 24 VDC
SD2000 OUT5 to OUT8 max. power rating
60 W DC
FEP2000N IN1 to IN4
15 VAC or 20 to 28 VDC / 3 A
Содержание 1200C