GE Security 1200C Скачать руководство пользователя страница 1

GE

 

Security 

 

P/N 1068351 • REV 10 • ISS 03JUN09 

1200C-2000C Fire Alarm Control 

Panel, Repeater, and Black Box 

Installation Manual 

Содержание 1200C

Страница 1: ...GE Security P N 1068351 REV 10 ISS 03JUN09 1200C 2000C Fire Alarm Control Panel Repeater and Black Box Installation Manual ...

Страница 2: ...ctive products Intended use Use this product only for the purpose it was designed for refer to the data sheet and user documentation for details For the latest product information contact your local supplier or visit us online at www gesecurity eu Certification and compliance 2002 96 EC WEEE directive Products marked with this symbol cannot be disposed of as unsorted municipal waste in the Europea...

Страница 3: ...nnecting the SD2000 common I O module 6 Connecting the FEP2000N main controller module 12 Connecting the NC2011 and NC2051 network modules 13 Connecting the LON2000 serial communication module 15 Connecting the ZE2016 and ZE2064 zone LED modules 16 Connecting the mains power supply 17 Connecting the batteries 24 Commissioning the control panel 26 Basic configuration options 29 Maintenance 30 Fire ...

Страница 4: ... and manual call points Compatibility with third party products cannot be guaranteed Consult your local supplier for further information Support For assistance installing operating maintaining and troubleshooting this product please contact your local supplier Limitation of liability Installation in accordance with this manual applicable codes and the instructions of the authority having jurisdict...

Страница 5: ...ing national standard and any other applicable regulations Cabinet layout for 1200C control panels Figure 1 Typical cabinet layout for 1200C control panels 1 FEP2000N mains controller module 2 PS1200N power supply interface module 3 LC1502 loop module 4 SD2000 common I O module 5 PS2000N power supply unit 6 Earth stud 7 Fuse terminal block 8 12V batteries For detailed module information for all co...

Страница 6: ...cal cabinet layout for 2000C control panels 1 FEP2000N mains controller module 2 Earth studs 3 PS1200N power supply interface module 4 LC1502 loop modules 5 SD2000 common I O module 6 12V batteries 7 Fuse terminal block 8 PS2000N power supply unit For detailed module information for all control panels see Appendix A Modules on page 35 ...

Страница 7: ...ical inside door layout for 1200C 2000C control panels 1 KP2000 keypad module 2 LCD1200 LCD screen 3 FC1200N or FC2012 host CPU module 4 NC2011 or NC2051 network module optional 5 ZE2016 or ZE2064 zone LED module 6 HDIS2000N or HDIS2000 F LED display module For detailed module information for all control panels see Appendix A Modules on page 35 ...

Страница 8: ...ifications on page 39 WARNING Failure to use the recommended cable may impact system performance Table 1 Recommended cables Cable Cable description Maximum cable length Mains cable 3 x 1 5 mm N A Loop cable Shielded twisted pair cable 2 km RS485 network cable CAT5 800 m Fibre optic network cable ST duplex 50 125 62 5 125 or 100 140 1 7 km see note below LON network cable CAT5 1 5 km RS232 serial c...

Страница 9: ...t box between the PS1200N module and the SD2000 or VDS2000 module Figure 4 LC1502 loop module 1 Loop Class configuration jumpers A and B 2 Class B loop 1 or Class A loop 1 out 3 Class B loop 2 or Class A loop 1 return 4 Class B loop 3 or Class A loop 2 out 5 Class B loop 4 or Class A loop 2 return Note For EN 54 compliance an isolator must be installed after every 32 devices Loop Class configurati...

Страница 10: ...he group It is connected to the LC1502 module Note This module is not included with French or German control panels Figure 5 SD2000 common I O module 1 IN5 fire routing return input VdS mode only 2 IN6 fire protection fault input VdS mode only 3 IN7 fire routing fault input VdS mode only 4 IN8 general input 5 OUT1 fire alarm equipment output 6 OUT2 fire routing equipment output 7 OUT3 fire protect...

Страница 11: ...ch relay has common C normally closed NC and normally open NO contacts Figure 6 Common I O module programmable relays 1 OUT8 programmable relay 4 LED 2 OUT7 programmable relay 3 LED 3 OUT6 programmable relay 2 LED 4 OUT5 programmable relay 1 LED 5 OUT8 programmable relay 4 6 OUT7 programmable relay 3 7 OUT6 programmable relay 2 8 OUT5 programmable relay 1 ...

Страница 12: ... loops 1 OUT4 fault routing output LED 2 OUT2 fire routing equipment output LED 3 OUT3 fire protection equipment output LED 4 OUT1 fire alarm equipment output LED 5 OUT4 fault routing output 6 OUT3 fire protection equipment output 7 OUT2 fire routing equipment output 8 OUT1 fire alarm equipment output Table 2 Supervised output specifications for Class A loops Output Output number termination Polar...

Страница 13: ...ut The relay behaviour is configured using jumpers J2 to J7 J12 to J13 and J18 to J19 on the module PCB Configuration of outputs 1 to 3 Jumper configuration options for relay outputs 1 to 3 are shown below Jumper configuration options for relay outputs 1 to 3 with Class B loops Output Output number Option 1 Option 2 Comments Sounder OUT1 J12 IN J12 OUT J18 OUT J13 OUT J13 IN J19 OUT Fire brigade O...

Страница 14: ...open when there is no fault Jumper configuration options for output 4 with Class B loops Output Output number Option 1 Option 2 Comments Fire routing OUT4 J6 IN J6 OUT J7 OUT J7 IN Figure 9 Jumper configuration options Supervised inputs The common I O module has four inputs Input function for EN NEN and EP modes In EN NEN and EP mode the four inputs have no dedicated function and are freely progra...

Страница 15: ...eneral input IN8 Fault routing fault input IN7 Fire protection fault input IN6 Fault routing return input IN5 Figure 10 Common I O module supervised inputs in VdS mode 1 IN5 general input OR fault routing return input VdS mode 2 IN6 general input OR fire protection fault input VdS mode 3 IN7 general input OR fault routing fault input VdS mode 4 IN8 general input ...

Страница 16: ...The FEP2000N main controller module is located in the rear cabinet It is the first module of the group and is connected to the PS1200N module Figure 11 Main controller module auxiliary inputs 1 IN4 auxiliary input 4 2 IN3 auxiliary input 3 3 IN2 auxiliary input 2 4 IN1 auxiliary input 5 FC1200N or FC2012 host CPU module connector ...

Страница 17: ...and connected to the FC1200N or FC2012 host CPU module General information All network nodes use the ARCNET protocol Every node on the network must have a network module installed Where cabling runs between buildings or in high noise or harsh environments a fibre optic network should be used NC2011 network module for RS485 networks Figure 12 NC2011 network module 1 Termination jumper 2 Shield 3 Ea...

Страница 18: ...14 1200C 2000C Fire Alarm Control Panel Repeater and Black Box Installation Manual NC2051 network module for fibre optic networks Figure 13 NC2051 network module ...

Страница 19: ...e P13 20 PIN male connector of the FC1200N or FC2012 host CPU module located on the inside of the control panel door Figure 14 LON2000 serial communication module 1 Service switch 2 Termination jumper J1 Termination If a LON2000 serial communication module is installed into the first or last control panel of a LON network then the termination jumper J1 must be inserted to terminate the communicati...

Страница 20: ...00C control panels The maximum number of zone modules that can be installed will depend on the control panel model see Appendix C Maximum zones and loops on page 38 for more information The ZE2016 and ZE2064 modules are located on the inside of the control panel door and are connected to the HDIS2000N or HDIS2000 F LED display module Caution The ZE2016 and ZE2064 zone LED modules must ntot be inst...

Страница 21: ...ice and only be used for fire detection equipment Caution Keep mains cables separate from other cabling to avoid potential short circuits and interference Always secure mains cables to the cabinet to prevent movement Figure 15 Typical power supply connections for a 1200C control panel 1 PS1200N power supply interface module 2 PS2000N power supply unit 3 Earth stud 4 Fuse terminal block 5 Incoming ...

Страница 22: ...nual PS2000N power supply unit connections The PS2000N is the main power supply unit for 1200C 2000C control panels and complies with all EN 54 requirements when used with these products Figure 16 PS2000N layout and connections 1 Fuse terminal block connector 2 PS1200N connector ...

Страница 23: ...l block connections The 230 VAC mains power supply is connected directly to the fuse terminal block as shown below Figure 17 Fuse terminal block connections 1 Earth stud 2 Fuse 3 Live wire 4 Incoming 230 VAC mains cable 5 Earth wire 6 Neutral wire 7 Cable connection to PS2000N power supply input ...

Страница 24: ...2 module Figure 18 PS1200N layout and connections 1 FC1200N or FC2012 host CPU module connector 2 Potentiometer LCD screen contrast 3 Modem power supply connector 4 Power supply fault relay output configuration jumpers J7 and J8 5 Power supply fault relay output 6 24 VDC auxiliary output 7 Internal printer power supply connector 8 Power and fault monitoring LEDs 9 Battery selection DIP switch 10 B...

Страница 25: ...gure 19 PS1200N fault relay jumper configurations 1 Normally open NO 2 Common C 3 Normally closed NC Note Components shown are mounted onto the PS1200N PCB and do not represent field wiring The fault output is normally closed The default setting for jumpers J7 and J8 is A Configuration options are J7 pins for position B connected on PCB Position A 3K3Ω Position B 0Ω J8 pins for position A connecte...

Страница 26: ... power is supplied by batteries or the module is without power Earth fault Yellow Indicates control panel earth faults If the LED is lit an earth fault has been detected Charger fault Yellow Indicates the general status of the battery charger If the LED is lit there is a fault with charging the batteries incorrect voltage temperature sensor connection fault microcontroller error etc Battery voltag...

Страница 27: ...r supply connections for repeaters 24 VDC power supply connectors for repeaters are located on the termination board Figure 21 24 VDC power supply connections 1 Fuse 2 24V connector 3 24V connector 4 Earth connector 5 Charger fail normally shorted input 6 Mains supply fail normally shorted input ...

Страница 28: ...d externally 12V 45 Ah Batteries must be installed externally Note 45 Ah batteries may not be used with FP1200C FR1200 or FR2000 panels Once batteries are installed the battery type must be set using the battery selection DIP switch See Charging batteries below Charging batteries In accordance with EN 54 4 installed batteries may be charged by the control panel To ensure correct charging the type ...

Страница 29: ...e control panel may be powered up using battery power To do this press the battery startup button on the PS1200N power supply interface module see Figure 18 on page 20 Third source power supply An optional 9V PP3 battery may be installed as a third source power supply The third source battery is connected to the FC1200N or FC2012 host CPU module ...

Страница 30: ...rrectly and that polarity has been observed Check that the lithium battery on the host CPU module is enabled jumper J5 located above the battery is inserted and unlock the memory Check that the control panel is well earthed at the earth terminals provided The earth must be directly wired to the distribution board earth This is required for safety and interference suppression Check that all repeate...

Страница 31: ... do not proceed Disconnect batteries and all field wiring and investigate the cause of the problem 6 The control panel will now perform internal checks and any faults detected will be displayed on the LCD screen The total number of faults is reported on line 8 Use the scroll button to view the faults See Table 6 below for a list of possible faults that may be reported 7 Any faults reported should ...

Страница 32: ...the systems on the ARCNET network that are configured to communicate with the repeater Faults regarding communication with repeater node identification address should disappear when the ARCNET network is operational 4 Check all connections to panels by emulating them 5 Check panel fault reporting by switching off each panel one by one and checking that the missing panel is reported by the other pa...

Страница 33: ...s with a VDS2000 module installed Language groups Each panel is shipped with one language group A language group may include up to five languages Table 7 1200C 2000C language groups Group 0 Group 1 Group 2 Group 3 Group 4 Group 5 English English English English English English Dutch Holland Polish Danish Lithuanian Italian Romanian Dutch Belgium Hungarian Swedish Estonian Spanish Greek French Czec...

Страница 34: ...s and corresponding connections Visually inspect the fire panel for signs of moisture or other deterioration Test the alarm fault and ancillary functions of the fire panel Annual Verification Carry out the recommended daily and quarterly inspection and test routines Check each detector for correct operation in accordance with the manufacturer s recommendations Visually inspect all cable fittings a...

Страница 35: ...ntrol panel event log does not indicate a mains failure in the last twenty four hours If the leads are in good condition all connections are correct and the control panel continues to report that the test has failed twenty four hours after the last mains failure then the batteries should be replaced immediately Replacing batteries To replace the batteries do the following 1 Disconnect and remove t...

Страница 36: ...ctors and or manual call points per panel 512 as defined by EN 54 2 Loop specifications 900 protocol Maximum number of loops per panel See Appendix C Maximum zones and loops on page 38 Loop overload current 500 mA Loop operating load Max 100 mA Maximum number of addressable devices per loop 126 per 2 km of cable Maximum number of addressable devices per panel including I O devices detectors and ma...

Страница 37: ...t battery cut out Earth fault Auxiliary supply fault Mains fail Charger fail Input voltage Earth fault Charger fault Battery loss Battery fault Mains fuse T 0 8A 250V T 1A 250V T 2A 250V Maximum current primary input 250 mA 0 3 A no options installed 1A Maximum output ripple voltage 300 mV 300 mV Fault relay subject to jumper configuration Maximum switching current 2A at 24 VDC Maximum power ratin...

Страница 38: ...city is calculated with the following formula C Standby current Standby time Alarm current Alarm time Calculation example for 24 hours standby time and 30 minutes in alarm System data 1 x zone module 250 mA at FEP2000N auxiliary output 1 x internal printer not supplied No modem 2 x loops with 100 devices per loop 100 mA at SD2000 sounders output Status System Aux Printer Modem Loops Sounders Total...

Страница 39: ...terface module PS1200N power supply interface module PS2000N power supply unit PSDC2000 24V power supply interface module NC2011 RS485 network module NE2011 RS485 network extension module LON2000 serial communications module Optional modules In addition to the above the following optional modules may also be installed if required NC2051 fibreoptic network module NE2051 fibreoptic network extension...

Страница 40: ...es Panel Modules FP1216N ZE2016 FEP2000N PS1200N LC1502 SD2000 PS2000N FP1264N ZE2064 FEP2000N PS1200N LC1502 SD2000 PS2000N FP28255C ZE2064 FEP2000N PS1200N LC1502 SD2000 PS2000N FP2864C ZE2016 FEP2000N PS1200N LC1502 SD2000 PS2000N Regional variants German panels have a VDS2000 module instead of the SD2000 module French panels do not have the SD2000 module Danish and Swedish panels have the LON2...

Страница 41: ...Traffic White Large 810 x 445 x 120 RAL9016 Traffic White Cabinet use for each type of control panel is as follows Table 12 1200C 2000C dimensions and weights Control panel Cabinet size Weight kg FP1216C Small 9 FP1264C Small 9 FR1216C Small 9 FR1264C Small 9 FP2864C Large 15 FP28255C Large 15 FR2064C Large 15 FR20255C Large 15 FRG20255C Large 15 GR2064C Large 15 Note Weight is approximate and exc...

Страница 42: ...f zones Maximum number of zone modules Maximum number of loops Maximum number of loop modules FP1216C 16 1 x ZE2016 4A 8B 2 x LC1502 FP1264C 64 1 x ZE2064 4A 8B 2 x LC1502 FR1216C 16 1 x ZE2016 N A N A FR1264C 64 1 x ZE2064 N A N A FP2864C 64 4 x ZE2016 8A 8B 4 x LC1502 FP28255C 255 4 x ZE2064 8A 8B 4 x LC1502 FR2064C 64 4 x ZE2016 N A N A FR20255C 255 4 x ZE2064 N A N A FRG20255C 255 4 x ZE2064 N...

Страница 43: ...eeds 800 m and or 32 nodes we recommend the use of fibre optic cabling End of line termination resistors need to be used to match the cable characteristic impedance to prevent reflections Maximum cable length bus and dual bus topology 800 m Maximum number of nodes bus and dual bus topology 32 When shielded cable is used shields must be earthed at one point only The shield of the cable must be cont...

Страница 44: ...mum number of nodes bus topology 32 RS232 null modem cable A 7 way null modem cable with full handshaking is used to connect the control panel to a PC The figure below shows the required DB9 control panel to PC female to female cable configuration The cable length should not exceed 12 m Figure 22 Null modem cable configuration Output connections from addressable supervised units We recommend that ...

Страница 45: ... 9 5 Disablement of addressable points 10 Test EN 54 2 compliance for 1200C 2000C control panels with the VDS2000 module Control panels with the VDS2000 module installed have the following options with requirements according to EN 54 2 Table 15 EN 54 2 options with requirements with the VDS2000 module Clause Description 7 8 Output to fire alarm devices 7 9 Output to fire routing equipment VDE0833 ...

Страница 46: ...tails of the CPD certification for 1200C 2000C fire panels and global repeaters are shown below Table 16 CPD certification for 1200C 2000C series fire panels and global repeaters Certification Certification body 1134 Certificate number 1134 CPD 069 Manufacturer GE Security B V Kelvinstraat 7 6003 DH Weert The Netherlands ...

Страница 47: ...1200C 2000C Fire Alarm Control Panel Repeater and Black Box Installation Manual 43 ...

Страница 48: ......