5-34
Location
Message Line
Description
S 5.1
SETPOINTS
ANALOG INPUT
The setpoints page 5 header. This page allows the setpoints related to the
analog input to be entered.
S 5.2
ANALOG INPUT:
DISABLED
This message allows the user to enable or disable the analog input
function.
Only message S 5.17 will appear if DISABLED is selected in message 5.2.
S 5.3
EDIT ANALOG
INPUT TITLE? NO
This setpoint allows the user to enter any name of up to 16 characters, for
the analog input. This name will then appear in the relevant displays. Use
the NEXT CHOICE key to select YES and store this, if you intend to assign
a name to the analog input.
If YES is selected in message S 5.3, a brief description on how to store titles is displayed followed by message S 5.4.
S 5.4
__ USER TITLE
The display shows that the 565 Relay is ready to have the analog input
name assigned. Press the LINE UP or LINE DOWN key to display each
letter of the alphabet, one at a time. When the desired letter is displayed,
press the NEXT CHOICE key to move the cursor to the next position.
Repeat the same procedure for each additional letter of the title. Once the
complete title is displayed, press the STORE key to save it in the 565
memory. After the STORE key has been pressed, the screen will return to
message S 5.3.
S 5.5
EDIT ANALOG
INPUT UNITS? NO
This setpoint allows the user to enter any name of up to 8 characters, for
the analog input unit. This name will then appear in the relevant displays.
Use the NEXT CHOICE key to select YES and store this, if you intend to
assign a name to the analog input units.
If YES is selected in message S 5.5 a brief description on how to store units is displayed followed by message S 5.6.
S 5.6
UNITS
This display appears when the 565 Relay is ready to have the analog input
unit name assigned. Enter the required unit name, such as “DEG C” on the
left hand side of the display, as described in message S 5.4. When the last
character is displayed, press the STORE key to return to message S 5.5.
S 5.7
MIN CURR SCALE
VALUE: 4.00
The 565 Relay has the ability to accept an analog input signal in the range
of 4-20 mA and this display asks for the scale factor which you intend to
use for the minimum analog input.
The quantity being monitored might be the temperature of a transformer
on the feeder. This input can be used to initiate alarms if it exceeds safe
levels. A scale factor can be chosen to change the displayed value from
milliamps to degrees centigrade. The use of the minimum scale factor is
shown by the following example. The 565 Relay logic is configured so that
the value which you will see displayed when the analog signal is 4 mA will
be the scale factor minimum value. Refer to the manufacturer’s instruc-
tions for the monitor or device to determine the temperature (or other
quantity) corresponding to its 4 mA output.
If this value is 50 degrees centigrade, for example, then set the minimum
scale factor at 50. Now when a 4 mA input is presented to the 565 Relay it
will display 50 indicating a temperature, which is more useful than a
milliamp reading.
The range of possible values for the minimum scale factor is 0 to 1023 in
L
A
L
A
L
A
L
A
L
A
L
A
L
A
SETPOINTS MODE - ANALOG INPUT
Содержание 565
Страница 6: ...INSTALLATION 2 2 Figure 2 1 Mounting Details ...
Страница 7: ...INSTALLATION 2 3 Figure 2 2 Mounting Arrangement with Relay Collar ...
Страница 12: ...INSTALLATION 2 8 Figure 2 5 565 Relay Typical Wiring ...
Страница 13: ...INSTALLATION 2 9 Figure 2 6 Voltage Sensing Wire ...
Страница 14: ...INSTALLATION 2 10 Figure 2 7A 565 with MTM CT and Open Delta VT Typical Wiring ...
Страница 15: ...INSTALLATION 2 11 Figure 2 7B 565 with MTM CT and Wye VT Typical Wiring ...
Страница 16: ...INSTALLATION 2 12 Figure 2 8A Open Delta VT and CT MTM Typical Wiring ...
Страница 17: ...INSTALLATION 2 13 Figure 2 8B Wye VT and CT MTM Typical Wiring ...
Страница 18: ...INSTALLATION 2 14 Figure 2 9 MTM Mounting Dimensions ...
Страница 19: ...INSTALLATION 2 15 Figure 2 10 565 Rear Panel Layout ...
Страница 20: ......
Страница 23: ...DISPLAY AND KEYBOARD 3 3 Figure 4 1 565 Relay Front Panel ...
Страница 28: ......
Страница 132: ......
Страница 142: ...CURVE INFORMATION ANDTABLES 7 10 Figure 7 9 IEC A Curves ...
Страница 143: ...CURVE INFORMATION ANDTABLES 7 11 Figure 7 10 IEC B Curves ...
Страница 144: ...CURVE INFORMATION ANDTABLES 7 12 Figure 7 11 IEC C Curves ...
Страница 176: ...RELAYTESTING 8 2 Figure 8 1 Secondary Injection Test Setup ...
Страница 180: ......
Страница 184: ......
Страница 192: ...APPENDIX C C 2 Figure C1 System Controller Block Diagram 1 2 ...
Страница 193: ...APPENDIX C C 3 Figure C2 System Controller Block Diagram 2 2 ...
Страница 194: ......
Страница 198: ......