4-9
Location
Message Line
Description
A 5.5
PHASE A PRE-TRIP
CURRENT 16100 A
This is the RMS current flowing in phase A measured over one cycle of
feeder current, at the time that the 565/575 Relay initiated the breaker trip.
A 5.6
PHASE B PRE-TRIP
CURRENT 15900 A
This is the RMS current flowing in phase B measured over one cycle of
feeder current, at the time that the 565/575 Relay initiated the breaker trip.
A 5.7
PHASE C PRE-TRIP
CURRENT 16200 A
This is the RMS current flowing in phase C measured over one cycle of
feeder current, at the time that the 565/575 Relay initiated the breaker trip.
A 5.8
GROUND PRE-TRIP
CURRENT 250 A
This is the RMS ground current sensed by the Relay measured over one
cycle of feeder current, at the time when the 565/575 Relay initiated the
breaker trip.
Messages A 5.9 to 5.11 will only appear if an Open Delta system is chosen in Setpoints mode.
A 5.9
PRE-TRIP VOLTAGE
A-B 13.80 kV
This is the voltage between phases A and B when the 565 Relay caused
the feeder breaker to trip due to a system fault.
A 5.10
PRE-TRIP VOLTAGE
B-C 13.80 kV
This is the voltage between phases B and C when the 565/575 Relay
caused the feeder breaker to trip due to a system fault.
A 5.11
PRE-TRIP VOLTAGE
C-A 13.80 kV
This is the voltage between phases C and A when the 565/575 Relay
caused the feeder breaker to trip due to a system fault.
Messages A 5.12 to 5.14 will only appear if a Wye system is chosen in Setpoints mode.
A 5.12
PRE-TRIP VOLTAGE
A-N 7.85 kV
This is the voltage between phase A and the neutral line when the 565/575
Relay caused the feeder breaker to trip due to a system fault.
A 5.13
PRE-TRIP VOLTAGE
B-N 7.85 kV
This is the voltage between phase B and the neutral line when the 565/575
Relay caused the feeder breaker to trip due to a system fault.
A 5.14
PRE-TRIP VOLTAGE
C-N 7.85 kV
This is the voltage between phase C and the neutral line when the 565/575
Relay caused the feeder breaker to trip due to a system fault.
A 5.15
FREQUENCY AT
TRIP 60.2 Hz
This is the feeder frequency, measured in Hz, at the time when the 565/
575 Relay caused the breaker to trip. If an MTM is communicating with the
565/575 at the time of the trip, the frequency recorded will be from the
MTM.
A 5.16
DATE OF TRIP
AUG 04,1992
This is the date when the 565/575 Relay last tripped the feeder breaker
due to a system fault.
A 5.17
TIME OF TRIP
14:20:42
This is the time when the 565/575 Relay last tripped the feeder breaker. It
is laid out in the following form:
Hour:Minute:Second
L
A
ACTUAL VALUES MODE - PRE-TRIP DATA
Содержание 565
Страница 6: ...INSTALLATION 2 2 Figure 2 1 Mounting Details ...
Страница 7: ...INSTALLATION 2 3 Figure 2 2 Mounting Arrangement with Relay Collar ...
Страница 12: ...INSTALLATION 2 8 Figure 2 5 565 Relay Typical Wiring ...
Страница 13: ...INSTALLATION 2 9 Figure 2 6 Voltage Sensing Wire ...
Страница 14: ...INSTALLATION 2 10 Figure 2 7A 565 with MTM CT and Open Delta VT Typical Wiring ...
Страница 15: ...INSTALLATION 2 11 Figure 2 7B 565 with MTM CT and Wye VT Typical Wiring ...
Страница 16: ...INSTALLATION 2 12 Figure 2 8A Open Delta VT and CT MTM Typical Wiring ...
Страница 17: ...INSTALLATION 2 13 Figure 2 8B Wye VT and CT MTM Typical Wiring ...
Страница 18: ...INSTALLATION 2 14 Figure 2 9 MTM Mounting Dimensions ...
Страница 19: ...INSTALLATION 2 15 Figure 2 10 565 Rear Panel Layout ...
Страница 20: ......
Страница 23: ...DISPLAY AND KEYBOARD 3 3 Figure 4 1 565 Relay Front Panel ...
Страница 28: ......
Страница 132: ......
Страница 142: ...CURVE INFORMATION ANDTABLES 7 10 Figure 7 9 IEC A Curves ...
Страница 143: ...CURVE INFORMATION ANDTABLES 7 11 Figure 7 10 IEC B Curves ...
Страница 144: ...CURVE INFORMATION ANDTABLES 7 12 Figure 7 11 IEC C Curves ...
Страница 176: ...RELAYTESTING 8 2 Figure 8 1 Secondary Injection Test Setup ...
Страница 180: ......
Страница 184: ......
Страница 192: ...APPENDIX C C 2 Figure C1 System Controller Block Diagram 1 2 ...
Страница 193: ...APPENDIX C C 3 Figure C2 System Controller Block Diagram 2 2 ...
Страница 194: ......
Страница 198: ......