5-16
Location
Message Line
Description
S 2.13
PHASE INST TRIP
DELAY INST
The intentional delay on the phase instantaneous trip is set here in the
range 0 to 40 cycles in steps of one cycle. If 0 is selected, INST will be
displayed and there will be no intentional delay. There is, however, a 1 cycle
delay which is necessary for the 565/575 relay to react to the fault
condition. If any other value is entered within the above range, the trip will
occur in this above reaction time plus the entered value. Thus, for an
entered delay of 2 cycles on a 60 Hz system, the actual time to trip on
phase instantaneous is 3 × 16.6 ms = 50 ms.
Definite time characteristics can be implemented by using the phase
instantaneous trip and appropriate time delays. For example, the phase
instantaneous trip setpoint can be enabled and a delay between 0–40
cycles programmed. This effectively will simulate a Definite Time curve.
S 2.14
PHASE INST TRIP
RELAY TRIP
This message allows the user to select the relay or combination of relays
which the trip generated in message S 2.11 will activate.
Messages S 2.15 to S 2.22 pertain to the 575 only. The remaining messages beginning at S 2.23 are for both the 565/575.
S 2.15
PH AUTOBLK INST
HISET DISABLED
This setpoint allows the user to enable or disable the phase autoblock
HISET feature.
Message S 2.16 will only appear if ENABLED is selected in message S 2.15.
S 2.16
PH AUTOBLK HISET
AFTER RECL.# 4
Determined after which reclosure the Phase Instantaneous Hiset Trip will
be disabled (blocked).
S 2.17
PHASE LOSET INST
TRIPS ENABLED
Same as PHASE HISET INST TRIP feature except any two phases must
be over the trip level to cause a trip.
Messages S 2.18 to S 2.22 will only appear if ENABLED is selected in message S 2.17.
S 2.18
PHASE LOSET INST
TRIPS 2.0 X P/U
Similar to PHASE HISET INST TRIP feature (see above).
S 2.19
PHASE LOSET INST
DELAY INST
Similar to PHASE HISET INST TRIP feature (see above).
S 2.20
PHASE LOSET INST
RELAY TRIP&AUX1
Select the desired output contact(s) to activate on a PHASE LOSET INST
TRIP.
S 2.21
PH AUTOBLK INST
LOSET DISABLED
This setpoint allows the user to enable or disable the phase autoblock
LOSET feature.
(575)
PHASE
HISET
INST
DELAY
INST
(575)
PHASE
HISET
INST
RELAY
TRIP&AUX1
SETPOINTS MODE - PHASE CURRENT
Содержание 565
Страница 6: ...INSTALLATION 2 2 Figure 2 1 Mounting Details ...
Страница 7: ...INSTALLATION 2 3 Figure 2 2 Mounting Arrangement with Relay Collar ...
Страница 12: ...INSTALLATION 2 8 Figure 2 5 565 Relay Typical Wiring ...
Страница 13: ...INSTALLATION 2 9 Figure 2 6 Voltage Sensing Wire ...
Страница 14: ...INSTALLATION 2 10 Figure 2 7A 565 with MTM CT and Open Delta VT Typical Wiring ...
Страница 15: ...INSTALLATION 2 11 Figure 2 7B 565 with MTM CT and Wye VT Typical Wiring ...
Страница 16: ...INSTALLATION 2 12 Figure 2 8A Open Delta VT and CT MTM Typical Wiring ...
Страница 17: ...INSTALLATION 2 13 Figure 2 8B Wye VT and CT MTM Typical Wiring ...
Страница 18: ...INSTALLATION 2 14 Figure 2 9 MTM Mounting Dimensions ...
Страница 19: ...INSTALLATION 2 15 Figure 2 10 565 Rear Panel Layout ...
Страница 20: ......
Страница 23: ...DISPLAY AND KEYBOARD 3 3 Figure 4 1 565 Relay Front Panel ...
Страница 28: ......
Страница 132: ......
Страница 142: ...CURVE INFORMATION ANDTABLES 7 10 Figure 7 9 IEC A Curves ...
Страница 143: ...CURVE INFORMATION ANDTABLES 7 11 Figure 7 10 IEC B Curves ...
Страница 144: ...CURVE INFORMATION ANDTABLES 7 12 Figure 7 11 IEC C Curves ...
Страница 176: ...RELAYTESTING 8 2 Figure 8 1 Secondary Injection Test Setup ...
Страница 180: ......
Страница 184: ......
Страница 192: ...APPENDIX C C 2 Figure C1 System Controller Block Diagram 1 2 ...
Страница 193: ...APPENDIX C C 3 Figure C2 System Controller Block Diagram 2 2 ...
Страница 194: ......
Страница 198: ......