CHAPTER 7: TESTING
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
7–9
A2 METERING DATA
ZV
ANALOG INPUTS
:
0 to 1 mA Analog Input
Z
Alter the following settings:
S12 ANALOG I/O
ZV
ANALOG INPUT1
Z
ANALOG INPUT1:
“
0-1 mA”
S12 ANALOG I/O
ZV
ANALOG INPUT1
ZV
ANALOG INPUT1 MINIMUM:
“0”
S12 ANALOG I/O
ZV
ANALOG INPUT1
ZV
ANALOG INPUT1 MAXIMUM:
“1000” (repeat for
Analog Inputs 2 to 4)
Analog output values should be
±
0.01 mA on the ammeter. Measured analog input
values should be
±
10 units.
Z
Force the analog outputs using the following settings:
S13 TESTING
ZV
TEST ANALOG OUTPUT
Z
FORCE ANALOG OUTPUTS FUNCTION:
“Enabled”
S13 TESTING
ZV
TEST ANALOG OUTPUT
ZV
ANALOG OUTPUT 1 FORCED VALUE:
“0%”
(enter desired percent, repeats for analog output 2-4)
Z
Verify the ammeter readings as well as the measured analog input
readings.
Z
View the measured values in:
A2 METERING DATA
ZV
ANALOG INPUTS
:
ANALOG
OUTPUT
FORCE
VALUE
EXPECTE
D
AMMETE
R
READING
MEASURED
AMMETER READING
(mA)
EXPECTED
ANALOG
INPUT
READING
MEASURED ANALOG
INPUT READING
(units)
1
2
3
4
1
2
3
4
0%
4 mA
0 mA
25%
8 mA
250 mA
50%
12 mA
500 mA
75%
16 mA
750 mA
100%
20 mA
1000 mA
ANALOG
OUTPUT
FORCE
VALUE
EXPECT
ED
AMMETE
R
READIN
G
MEASURED
AMMETER
READING (mA)
EXPECTED
ANALOG
INPUT
READING
MEASURED ANALOG
INPUT READING
(units)
1
2
3
4
1
2
3
4
0%
0 mA
0 mA
25%
0.25 mA
250 mA
50%
0.50 mA
500 mA
75%
0.75 mA
750 mA
100%
1.00 mA
1000 mA
Содержание 469
Страница 62: ...2 16 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 2 INTRODUCTION ...
Страница 89: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 90: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 292: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 294: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 313: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 315: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 9 808712A1 CDR ...
Страница 320: ...A 14 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A APPENDIX ...