469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
General Switch A to D
PATH: SETTINGS
ZV
S3 DIGITAL INPUTS
ZV
ASSIGNABLE INPUT 1(4
)
These settings apply only if the
INPUT 1(4) FUNCTION
is “General Switch A”. Similar messages
appear for General Switches B, C, and D.
There are four general switch functions assignable to the four digital inputs. Once a
general switch function is chosen for one of the digital inputs, the settings messages
shown here follow the assignment message. An alarm and/or trip may then be configured
for that input. The alarm and/or trip may be assigned a common name and a common
block time from motor start if required (if the alarm is to be disabled until some period of
time after he motor has been started). A value of “0” for the
BLOCK TIME
settings indicates
that the feature is always active, when the motor is stopped or running. The switch may
also be defined as normally open or normally closed. After the block delay has expired, the
digital input will be monitored. If the switch is not in its normal state after the specified
delay, an alarm or trip will occur.
Capture Trace
PATH: SETTINGS
ZV
S3 DIGITAL INPUTS
ZV
ASSIGNABLE INPUT 1(4)
ASSIGNABLE
[
INPUT 1 FUNCTION:
General Sw. A
Range: See above
MESSAGE
SWITCH NAME:
General Sw. A
Range: 12 alphanumeric characters
MESSAGE
GENERAL SWITCH A:
Normally Open
Range: Normally Open,
Normally Closed.
MESSAGE
BLOCK INPUT
FROM START: 0 s
Range: 0 to 5000 s in steps of 1
MESSAGE
GENERAL SWITCH A
ALARM: Off
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN ALARM
RELAYS:
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
MESSAGE
GENERAL SWITCH A
ALARM DELAY: 5.0
Range: 0.1 to 5000.0 s in steps of 0.1
MESSAGE
GENERAL SWITCH A
EVENTS: Off
Range: On, Off
MESSAGE
GENERAL SWITCH A
TRIP: Off
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN TRIP
RELAYS:
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3
MESSAGE
GENERAL SWITCH A
TRIP DELAY: 5.0 s
Range: 0.1 to 5000.0 s in steps of 0.1
ASSIGNABLE
[
INPUT 1 FUNCTION:
Capture Trace
Range: See above.
Содержание 469
Страница 62: ...2 16 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 2 INTRODUCTION ...
Страница 89: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 90: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 292: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 294: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 313: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 315: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 9 808712A1 CDR ...
Страница 320: ...A 14 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A APPENDIX ...