6–34
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES
The event recorder stores motor and system information each time an event occurs. An
event description is stored along with a time and date stamp for troubleshooting purposes.
Events include all trips, any alarm optionally (except Service Alarm, and 469 Not Inserted
Alarm, which always records as events), loss of control power, application of control power,
emergency restarts, and motor starts when a blocking function is active. The latter event
could occur if the block start contacts were shorted out to bypass the 469 and start the
motor.
EVENT 01
is the most recent event and
EVENT 256
is the oldest event. Each new event
bumps the other event records up one until
EVENT 256
is reached. The event record in
EVENT 256
is lost when a new event occurs. This information can be cleared using the
S1 469
SETUP
ZV
CLEAR DATA
ZV
CLEAR EVENT RECORD
settings.
MESSAGE
POWER FACTOR
EVENT01: 0.00
Range: 0.01 to 0.99 Lead or Lag, 0.00,
1.00 Not seen if VT Connection
is set as None.
MESSAGE
TORQUE
EVENT01: 0.0 Nm
Range: 0 to 999999.9. Seen only if
Torque Metering is Enabled
MESSAGE
ANALOG I/P 1
EVENT01: 0 Units
Range: –50000 to 50000. Not seen if
Analog Input 1 is Disabled.
MESSAGE
ANALOG I/P 2
EVENT01: 0 Units
Range: –50000 to 50000. Not seen if
Analog Input 2 is Disabled.
MESSAGE
ANALOG I/P 3
EVENT01: 0 Units
Range: –50000 to 50000. Not seen if
Analog Input 3 is Disabled.
MESSAGE
ANALOG I/P 4
EVENT01: 0 Units
Range: –50000 to 50000. Not seen if
Analog Input 4 is Disabled.
Table 6–3: Cause of Events (Sheet 1 of 2)
TRIPS
Acceleration Trip
Analog Diff 1-2 Trip
Analog Diff 3-4 Trip
Analog I/P 1 Trip
Analog I/P 2 Trip
Analog I/P 3 Trip
Analog I/P 4 Trip
Current U/B Trip
Differential Trip
General Sw.A Trip
General Sw.B Trip
General Sw.C Trip
General Sw.D Trip
Ground Fault Backup
Ground Fault Trip
Incomplete Seq Trip
Load Shed Trip
Mechanical Jam Trip
Overload Trip
Overvoltage Trip
Phase Reversal Trip
Power Factor Trip
Pressure Sw. Trip
Reactive Power Trip
Remote Trip
Reverse Power Trip
RTD 1 Trip
RTD 2 Trip
RTD 3 Trip
RTD 4 Trip
RTD 5 Trip
RTD 6 Trip
RTD 7 Trip
RTD 8 Trip
RTD 9 Trip
RTD 10 Trip
RTD 11 Trip
RTD 12 Trip
Short Circuit Backup
Short Circuit Trip
Single Phasing
(Unbalanced)
Speed Switch Trip
Tachometer Trip
Undercurrent Trip
Содержание 469
Страница 62: ...2 16 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 2 INTRODUCTION ...
Страница 89: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 90: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 292: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 294: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 313: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 315: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 9 808712A1 CDR ...
Страница 320: ...A 14 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A APPENDIX ...