5–108
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Two additional acceleration timers are provided for the two speed motor feature. One
timer is for a start in Speed 2 from a stopped condition. The other is an acceleration timer
for the transition from Speed 1 to Speed 2. Also, while the motor is running, the 469 will
ignore Mechanical Jam protection during the acceleration from Speed 1 to Speed 2 until
the motor current has dropped below Speed 2 FLA
×
Overload Pickup value, or the Speed
1-2 acceleration time has expired. At that point in time, the Mechanical Jam feature will be
enabled with the Speed 2 FLA.
MESSAGE
SPEED SWITCH TRIP
SPEED2 DELAY: 5.0
Range: 1.0 to 250.0 s in steps of 0.1.
Seen only if one of the digital
inputs is assigned as Speed
Switch
MESSAGE
SPEED2 RATED
SPEED:
Range: 100 to 7200 RPM in steps of 1.
Seen only if one of the digital
inputs is assigned as
Tachometer.
Содержание 469
Страница 62: ...2 16 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 2 INTRODUCTION ...
Страница 89: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 90: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 292: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 294: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 313: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 315: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 9 808712A1 CDR ...
Страница 320: ...A 14 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A APPENDIX ...