Take care of the pellet. Do not damp or crush it or it will affect the efficiency and the dust will 
be collected on the door glass. 

Installation   

 
1. Deciding where to Locate your Pellet Appliance: 

When installing this unit on a combustible floor (for example linoleum, hardwood flooring) a 
non-combustible  hearth  pad 

(15mm  thickness)

  must  be  under  the  unit  suitable  to 

withstand  the  weight  of  the  appliance.  The  pad  must  extend  at  least  the  width  of  the 
appliance [22” (558 mm)] and at least the depth of the appliance plus 6” (153 mm) in front of 
the appliance [29 3⁄4” (756 mm)]. 
 

The clearance between the walls or to the top should be no less 

than the size in the figure.         

       

 

 

 

 

 

 
                                     

Min. installation clearance (mm)

 

2  Electrical: 

The unit must be grounded (earthed). The grounded electrical cord should be connected to a 
standard 230V, 50Hz electrical outlet.    Be careful that the electrical cord is not trapped under 
the  appliance  and  that  it  is  clear  of  any  hot  surfaces  or  sharp  edges  and  also  must  be 
accessible. If this power cord should become damaged, a replacement power cord must be 
purchased from a reputable dealer.   

 

3  Air input and venting pipe Installation 

Before setting out to installing the appliance, it is imperative that all national and 
local  regulations  and  European  Standards  are  complied  with      Please  consult 
with local government and authorities as necessary. 

 

Содержание HP24

Страница 1: ...estrictions and installation inspection requirements in your area PLEASE READ THIS ENTIRE MANUAL BEFORE INSTALLATION AND USE OF THIS PELLET BURNING ROOM HEATER FAILURE TO FOLLOW THESE INSTRUCTIONS COU...

Страница 2: ...6 9 Troubleshooting 17 10 Warranty 18 11 Figure Electricity control 19 Technical Specification Stove Mass 98 kg Nominal output Maximum setting Total Efficiency 92 3 Nominal Heat Output 9 4 kW Mean CO...

Страница 3: ...ed pellet type P F I PELLET STANDARDS Fines fine particles 1 maximum through a 3 mm 1 8 screen Bulk Density 650 kg m3 minimum Size 6 mm to 8 mm diameter 12mm to 35 mm long Ash Content 1 maximum Premiu...

Страница 4: ...s The stove s exhaust system works with negative combustion chamber pressure and a slightly positive chimney pressure A chimney draught of 12 Pa can be regarded as typical when operating at maximum ou...

Страница 5: ...sposed ashes should be placed in a metal container The closed container of ashes should be on a non combustible floor on the ground well away from all combustible materials pending final disposal If t...

Страница 6: ...T DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE FRESH AIR Outside Fresh Air connection is optional It must be connected to all units installed in Mobile and Air Tight Homes R200...

Страница 7: ...ature is still above 120 F 52 C Product performance The pellet stove has an advanced designed and has individual fresh air input and venting system Negative pressure burning technology causes high eff...

Страница 8: ...clearance between the walls or to the top should be no less than the size in the figure Min installation clearance mm 2 Electrical The unit must be grounded earthed The grounded electrical cord should...

Страница 9: ...fumes into the room The stove air input pipe diameter is 50 mm venting pipe diameter is 80 mm The total length of pipes is not longer than 3m Indoor venting pipe joint should be sealed by silicone sea...

Страница 10: ...Page 10 19...

Страница 11: ...l Temp and Weekly 5 TIMER BUTTON Order the start time or shutdown time of the unit Press Timer then set the period of time you needed attention the maximum is 7 hours Minimum is 1 hour After setting 5...

Страница 12: ...WEEKLY PROGRAMMER Temperature Units Blower Voltage and Exhaust Voltage Restore default setting and use Diagnostic platform are also access 8 CONCEL BUTTON 9 UP AND DOWN BUTTON Three status s descript...

Страница 13: ...TEMPERATURE 5 MAIN MODE HEATING POWER LEVEL IGNITOR COMBUSTION BLOWER blower AUGER CONVECTION BLOWER VACUUM SWITCH LIMIT SWITCH ON OFF STATE ADDITIONAL CONTROL MODE MAIN MODE DATE and TIME WORK STAGE...

Страница 14: ...The stove will power off and the fire will be put out when the auger motor stops b The stove will power off and the fire will be put out when the convection blower stops c Auger motor stops feeding w...

Страница 15: ...round the stove when it is operating 3 When installing this unit on a combustible floor for example linoleum hardwood flooring a non combustible hearth pad 15mm thickness with sufficient load bearing...

Страница 16: ...way any fly ash that may have collected on the heat exchanger tubes 5 Put the ash in the ash drawer out TIMELY 6 When the appliance is not to be used for a long time it should be cleaned completely Es...

Страница 17: ...ht the high temperature switches connection Change the high temperature switch D Three lights aren t bright No 220V power Pellet feeder is power off The wires of start and clock unit loose or break Ch...

Страница 18: ...own the blower Clean the heat exchange tubes 8 Ash and smoke fly out Leak between the connection of convection motor and venting pipe The clean method is wrong Use silicon rubber to seal Clean the dus...