High temperature switch 
(93˚C) is wrong. 

Cool  the  stove  at  least  1  hour  then 
operate  again  or  change  the  high 
temperature switch (93˚C). 

6. The blower still works 
after  the  stove  is  cool 
and fuel feed stops. 

The  low  temperature 
switch (50˚C) is broken. 

Change this switch. 

7.no enough heat wind    Unqualified    fuel 

Blower  speed  is  too 
high. 
Heat exchange tubes are 
dirty. 

Use the standard specially pellet. 
Turn down the blower. 
Clean the heat exchange tubes. 

8. Ash and smoke fly out.  Leak 

between 

the 

connection of convection 
motor and venting pipe.   
The  clean  method  is 
wrong. 

Use silicon rubber to seal. 
Clean the dust in the stove with brush 
to ash drawer.   

 
 
 

Warranty   

The problems caused by the owner’s improper operation are not our guarantee.    We 
can supply payment service. 
 
This appliance requires regular maintenance by a competent engineer. 

Use only replacement parts recommended by the manufacturer. 

NO

 unauthorized modification of this appliance should be carried out.    This would 

invalidate the warranty 

 
 
Electricity control

 

Содержание HP24

Страница 1: ...estrictions and installation inspection requirements in your area PLEASE READ THIS ENTIRE MANUAL BEFORE INSTALLATION AND USE OF THIS PELLET BURNING ROOM HEATER FAILURE TO FOLLOW THESE INSTRUCTIONS COU...

Страница 2: ...6 9 Troubleshooting 17 10 Warranty 18 11 Figure Electricity control 19 Technical Specification Stove Mass 98 kg Nominal output Maximum setting Total Efficiency 92 3 Nominal Heat Output 9 4 kW Mean CO...

Страница 3: ...ed pellet type P F I PELLET STANDARDS Fines fine particles 1 maximum through a 3 mm 1 8 screen Bulk Density 650 kg m3 minimum Size 6 mm to 8 mm diameter 12mm to 35 mm long Ash Content 1 maximum Premiu...

Страница 4: ...s The stove s exhaust system works with negative combustion chamber pressure and a slightly positive chimney pressure A chimney draught of 12 Pa can be regarded as typical when operating at maximum ou...

Страница 5: ...sposed ashes should be placed in a metal container The closed container of ashes should be on a non combustible floor on the ground well away from all combustible materials pending final disposal If t...

Страница 6: ...T DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE FRESH AIR Outside Fresh Air connection is optional It must be connected to all units installed in Mobile and Air Tight Homes R200...

Страница 7: ...ature is still above 120 F 52 C Product performance The pellet stove has an advanced designed and has individual fresh air input and venting system Negative pressure burning technology causes high eff...

Страница 8: ...clearance between the walls or to the top should be no less than the size in the figure Min installation clearance mm 2 Electrical The unit must be grounded earthed The grounded electrical cord should...

Страница 9: ...fumes into the room The stove air input pipe diameter is 50 mm venting pipe diameter is 80 mm The total length of pipes is not longer than 3m Indoor venting pipe joint should be sealed by silicone sea...

Страница 10: ...Page 10 19...

Страница 11: ...l Temp and Weekly 5 TIMER BUTTON Order the start time or shutdown time of the unit Press Timer then set the period of time you needed attention the maximum is 7 hours Minimum is 1 hour After setting 5...

Страница 12: ...WEEKLY PROGRAMMER Temperature Units Blower Voltage and Exhaust Voltage Restore default setting and use Diagnostic platform are also access 8 CONCEL BUTTON 9 UP AND DOWN BUTTON Three status s descript...

Страница 13: ...TEMPERATURE 5 MAIN MODE HEATING POWER LEVEL IGNITOR COMBUSTION BLOWER blower AUGER CONVECTION BLOWER VACUUM SWITCH LIMIT SWITCH ON OFF STATE ADDITIONAL CONTROL MODE MAIN MODE DATE and TIME WORK STAGE...

Страница 14: ...The stove will power off and the fire will be put out when the auger motor stops b The stove will power off and the fire will be put out when the convection blower stops c Auger motor stops feeding w...

Страница 15: ...round the stove when it is operating 3 When installing this unit on a combustible floor for example linoleum hardwood flooring a non combustible hearth pad 15mm thickness with sufficient load bearing...

Страница 16: ...way any fly ash that may have collected on the heat exchanger tubes 5 Put the ash in the ash drawer out TIMELY 6 When the appliance is not to be used for a long time it should be cleaned completely Es...

Страница 17: ...ht the high temperature switches connection Change the high temperature switch D Three lights aren t bright No 220V power Pellet feeder is power off The wires of start and clock unit loose or break Ch...

Страница 18: ...own the blower Clean the heat exchange tubes 8 Ash and smoke fly out Leak between the connection of convection motor and venting pipe The clean method is wrong Use silicon rubber to seal Clean the dus...

Страница 19: ...Page 19 19...

Отзывы: