ALUBOX X-treme MODEL BOILERS ARE DESIGNED
TO WORK ONLY WITH NATURAL GAS.
THEY CANNOT BE USED WITH LPG.
min.
max.
min.
max.
min.
max.
min.
max.
min.
max.
min.
max.
CO2 emission
%
9,11
9,16
9,16
9,15
8,69
8,91
8,83
9,13
8,91
9,09
8,95
9,07
Gas Consumption
m³/h
6,93
35,23
8,84
44,6
10,75
53,47
8,45
64,52
12,09
69,82
13,99
71,78
Flue gas mass flow
g/sec.
31
154
40
201
47
238
39
271
54
308
63
314
ALUBOX
X-TREME 710
ALUBOX
X-TREME LX 700
G20
ALUBOX
X-TREME 350
ALUBOX
X-TREME 430
ALUBOX
X-TREME 535
ALUBOX
X-TREME 640
10
COMBUSTION ADJUSTMENTS
These combution settings mentioned below must
be issued by authorized GASSERO services.
Flue gas analyzer must be used during to the
combustion adjustments.
ALUBOX X-treme
boilers are offer to sale after all required
combusiton, efficiency and safety controls. Emission settings
mustn’t be changed which are made by GASSERO. However, if
there is a deviation in the values which are given below, emission
settings should be changed by GASSERO authorized service.
10.1
EMISSION SETPOINTS
39