4.2.7
DEPOSIT AND DIRT SEPARATOR
To remove the dirt and particles form the water, a strainer or
deposit and dirt separator must be placed on the return line of the
boiler.
When the dirt, particles and similar deposits in the system
water are not cleaned;
The efficiency of the system decreases,
Installation equipments (pumps, valves, plate heat exchanger,
etc.) may be damaged due to overheating
A boiler damage may occur due to heat exchanger clogging.
Manufacturer cannot be held liable for damages that may
occur in such cases.
Strainers or deposit and dirt sepertors on the
system should be checked frequently and cleaned if
necessary.
4.2.8
AIR INLET FILTER (OPTIONAL)
If
ALUBOX X-treme
boilers will be used in to a dirty air
environment, they must be supported with the air inlet filters. This
optional filter must be checked regularly.
When the air inlet filter becomes dirty;
Emission values would be deteriorated and efficient
combustion wouldn’t be achieved.
The accumulation of soot occurs in the heat exchanger.
Loud ignition and combustion occurs.
Overheating, leakage and deformation would be observed in
the flue system.
Manufacturer cannot be held liable for damages
caused by dirty combustion air.
Don’t block the air filter partially or totally.
4.2.9
PUMP
Pumps aren’t included in
ALUBOX X-treme
model boilers. The
primary pumps, which are determined according to the hydraulic
pressure losses of the boiler, are offered by Gassero as an option.
If a different primary pump is to be used, pump must be selected
in accordance with the values given in the table on the below.
min
max
mwc
ALUBOX X-TREME 350
3,052
15,2
5
ALUBOX X-TREME 430
3,941
19,286
6
ALUBOX X-TREME 535
5,281
23,454
6
ALUBOX X-TREME 640
3,935
28,389
6
ALUBOX X-TREME LX 700
5,54
30,31
5
ALUBOX X-TREME 710
6,65
30,43
6
WATER FLOW
(m3/h)
19