Page 15
810-PS2 Manual
display enclosure and route the 2 feet of Synflex from there
(see diagram below). If alarm wiring is to be connected, drill
and tap extra holes as needed into the enclosure. Make sure
any unused holes in the enclosure are plugged. Feed the fiber
optic cable through the hose, leaving about 12 inches extra at
each end.
MODEL 810
LIQUID LEVEL GAUGE
MADE IN CANADA
UNITS
S
EE
L
EVE
L
GARNET
INSTRUMENTS LTD.
24" length
Display shown with lid and bracket removed.
8.
Cut the fiber ends square with a sharp knife and insert the fiber
into the connectors at each end and tighten the connector
lock nuts. The display should change from reading “no L” (no
light) to some inch value as soon as the fiber is connected. If
not, check that the fiber ends are clean and cut square, and
that the fiber is fully inserted into the connectors at each end.
If the display shows bL: 8 or bL:11 then the display and bar are
not programmed for the same mode.
9.
Inspect the head cap for casting flash, and lightly sand or
scrape off any casting protrusions. Make sure that there is
grease on the rubber O-ring and snap on the head cap.
10. Program the gauge as directed in the programming section.
To determine the bottom reading of the gauge, measure from
the bottom of the tank to 2/3 way up of the straight vertical
part of the float when the float is resting on the anchor. Do
NOT
set the gauge to read “0” at the bottom since this will not
result in a correct reading when the float is actually floating on
the product. In addition, if the gauge ever goes below “0” due
to tank expansion, it will read some nonsensical value since
this region has not been programmed.