Gardner Denver
6 Setting
the pressure bands
17
6.5
Setting the p2 Pressure Band
1) Touch
Settings > Control >
, then
p2
Target Pressure
or
p2 Cut-In Point
.
2) Use the keypad which will appear to enter your
desired setting (the permissible pressure limits are
displayed on the keypad screen).
3) Confirm the entry by pressing
OK
.
The display will revert to the previous screen.
4) Touch
p2 Cut-Out Point
.
Note
The upper pressure setting must be at least 0.3 bar
higher than the lower pressure setting.
The controller checks whether the value set can be
used. To prevent excessive wear of your compressor,
the difference should preferably be no less than 0.5 bar.
5) Enter your required setting using the keypad.
6) Confirm the entry by pressing
OK
.
VS