13-21-616 v00 Page 60
Discharge
Temperature
AEON 4000
Change Interval
AEON 9000SP
Change Interval
Up to 180
F (82
C)
4000 hrs.
8000 hrs.
180
F to 190
F (82
C to 88
C)
3000 hrs.
6000 hrs.
190
F to 200
F (88
C to 93
C)
2000 hrs.
4000 hrs.
200
F+ (93
C)
1000 hrs.
2000 hrs.
Figure 5-6 OIL CHANGE INTERVAL
Figure 5-7
– OIL SAMPLING VALVE LOCATION
303EBG797-00
(Ref. Drawing)
Содержание ELECTRA-SAVER
Страница 41: ...13 21 616 v00 Page 40 FIGURE 4 6 COMPRESSOR PACKAGE P ID 300EBF797 EB Ref Drawing...
Страница 55: ...13 21 616 v00 Page 54 300EBF797 EB Ref Drawing Figure 5 3 FLOW DIAGRAM AIR OIL SYSTEM...
Страница 56: ...13 21 616 v00 Page 55 301EBG797 00 Ref Drawing Figure 5 4 OIL FLOW DIAGRAM REMOTE MOUNTED COOLER...