background image

13-21-616 v00     Page 16 

 

Extreme Cold Weather Operation 

(Down To -10

F, -23

C

In addition to the above, the following should be provided: 

1. 

It will be necessary to provide shutters or to block off part of the cooler in some manner since the cooler 
is  greatly  oversized  for  operation  in  these  low  temperatures.  Since  shutters  are  not  provided  as  a 
factory option, blocking off a portion of the cooler with plywood should be satisfactory. 

 

2. 

Auto operation should not be used in extreme environments. 

 

3. 

Some  means  of  providing  heat  during  shutdown.  Start-up  should  be  provided.  There  are  various 
methods to accomplish this, but since openings are not provided for sump heaters, the use of radiant 
heaters is recommended.  The heaters should be sized to provide at least a +10

 

F (-12 C) environment 

for  coolers,  motor  and  sump.  Figure  2-3,  page  15,  shows  how  these  might  be  located  in  a  typical 
installation and sizes required. 

 

Remember  unsheltered  (outside)  installations  should  be  avoided  where  possible.  Installation  next  to  a 
heated building where enough heat can be used to keep the compressor room above freezing will save 
many complications in the operation and installation of the unit. 

 

Refer to Engineering Data Sheet 13-9-411, available from an authorized Gardner Denver distributor, for the 
advantages of using the heat recovered from rotary compressors. This heat recovery could easily pay for 
an adequate shelter for the unit. 

 

AUXILIARY  AIR  RECEIVER 

-  An  auxiliary  air  receiver  is  not  required  if  the  piping  system  is  large  and 

provides  sufficient  storage  capacity  to  prevent  rapid  cycling.  When  used,  an  air  receiver  should  be  of 
adequate size, provided with a relief valve of proper setting, a pressure gauge and a means of draining 
condensate. 

 

OPTIONAL MOISTURE SEPARATOR/TRAP 

– The unit can be provided with an optional stand-alone 

moisture separator and trap that is field-installed downstream of the aftercooler. 

 

CONTROL PIPING 

- Control piping is not necessary since the Rotary Screw compressor unit is factory 

wired and piped for the control system specified. 

 

INLET LINE 

- Where an inlet line is used between the air filter and the compressor, it must be thoroughly 

cleaned  on the inside to  prevent  dirt  or  scale  from  entering  the  compressor. 

If  welded construction  is 

used, the line must be shot blasted and cleaned to remove welding scale. 

In either case, the inlet line 

must be coated internally by galvanizing or painting with a moisture and oil-proof sealing lacquer. Up to ten 
(10) feet (3 meters) in length, the inlet line should be the full size of the inlet opening on the compressor. If an 
extra-long line is necessary, the pipe size should be increased according to Inlet Line Length Chart below 
in Figure 2-4. 

 

Accessibility  for inlet air  filter  servicing  must  be  considered  when  relocating  the  filters  from  the  unit  to a 
remote location. 

 

 

INLET LINE LENGTHS 

 

Length of Inlet Line

 

Diameter of Pipe Size

 

 

0 to 10 Feet (0 to 3 Meters)......................... Same as Compressor Inlet Opening 

10 to 17 Feet (3 to 5 Meters) ........................ One Size Larger Than Inlet Opening 
17 to 38 Feet (5 to 11.5 Meters)................... Two Sizes Larger Than Inlet Opening 

Figure 2-4   INLET LINE LENGTHS 

Содержание ELECTRA-SAVER

Страница 1: ...A SAVER SAVER II G2 BASE MOUNTED COMPRESSOR SAV125 150G2A ST125 200G2A Operating Service Manual MODELS SAVG2 125 STG2 125 125 HP SAVG2 150 STG2 150 150 HP STG2 200 200 HP 13 21 616 Version 00 October...

Страница 2: ...he necessary parts to simplify servicing your compressor Authorized distributor service technicians are factory trained and skilled in compressor maintenance and repair They are ready to respond and a...

Страница 3: ...nomical operation and minimum downtime Boxed text formats are used within this manual to alert users of the following conditions Safety Labels are used within this manual and affixed to the appropriat...

Страница 4: ...uipment in De Energized State Do Not Lift Equipment with Hook No Lift Point Handle Package at Forklift Points Only Loud Noise Hazard Wear Ear Protection Read the Operator s Manual before Proceeding wi...

Страница 5: ...or oil system until the unit is shut down and the air pressure has been relieved Electrical shock can and may be fatal Perform all wiring in accordance with the National Electrical Code NFPA 70 and a...

Страница 6: ...formation 8 Section 2 Installation 12 Section 3 Starting Operating Procedures 22 Section 4 Controls Instrumentation 33 Section 5 Lubrication Oil Cooler Oil Filter Separator 51 Section 6 Air Filter 71...

Страница 7: ...ing 62 Oil Sampling Valve 60 Oil Separator Compressor GD Eliminator 67 Inspection 68 Oil Carryover 67 Pressure Differential Gauging 68 Removal For Inspection Or Replacement 69 Oil Specifications 51 Oi...

Страница 8: ...een 31 Figure 3 10 Jogs Motor Screen 32 Figure 4 1 Controller Keypad 33 Figure 4 2 Schematic Tubing Diagram 34 Figure 4 3 Minimum Discharge Pressure Check Valve 35 Figure 4 4 Turn Valve Electra Saver...

Страница 9: ...ins as rotors unmesh at the inlet port and air is drawn into the cavity between the main rotor lobes and secondary rotor grooves A When the rotors pass the inlet port cutoff air is trapped in the inte...

Страница 10: ...discharges into the compressor main oil gallery A portion of the oil is directed through internal passages to the bearings gears and shaft oil seal The balance of the oil is injected directly into th...

Страница 11: ...13 21 616 v00 Page 10 Figure 1 4 COMPRESSOR MOTOR SIDE 125 150 HP Figure 1 4a COMPRESSOR MOTOR SIDE 200 HP 300EBG797 00 Ref Drawing...

Страница 12: ...13 21 616 v00 Page 11 Figure 1 5 COOLER RESERVOIR SIDE Figure 1 6 AIR OIL FLOW DIAGRAM 300EBG797 00 Ref Drawing 307EBD797 EA Ref Drawing...

Страница 13: ...e of air In some cases it may be necessary to install the air filter at some distance from the compressor to obtain proper air supply Do not electric weld on the compressor or base bearings can be dam...

Страница 14: ...ing Air is drawn in on the motor side of the unit and is exhausted through the roof on the separator side of the unit Do not block the air flow to and from the unit Allow three and one half 3 1 2 feet...

Страница 15: ...piping rigidity angle of tilt or danger of shifting from outside vibration or moving vehicles may require the use of mounting bolts and shims to provide uniform support for the base OIL RESERVOIR DRA...

Страница 16: ...will depend on the severity of the environment The following are general guidelines for outside installations Cold Weather Down To 10 F 12 C 1 Be sure all drains traps and control lines including pre...

Страница 17: ...eceiver is not required if the piping system is large and provides sufficient storage capacity to prevent rapid cycling When used an air receiver should be of adequate size provided with a relief valv...

Страница 18: ...ischarge service line to allow the unit to be safely isolated during service If a rotary screw and a reciprocating compressor are manifolded together an air receiver must be located between the two un...

Страница 19: ...PIPING Water Cooled Heat Exchanger Models Only On machines equipped with water cooled heat exchangers the water inlet and outlet connections are located in the unit enclosure flange on the end of the...

Страница 20: ...water warmer than 90 F 32 C is used higher compressor oil inlet temperatures and high water usage will result Most water systems will require control of impurities filtration softening or other treatm...

Страница 21: ...pressor package is factory wired for all connections from the starter to the motor for the horsepower and voltage specified on the order The standard unit is supplied with open drip proof motors and a...

Страница 22: ...filled with Mobil Polyrex EM 5 Leave the relief plug temporarily off Reconnect the unit and run for about 20 minutes to expel the excess grease 6 Stop the unit Replace the relief plug 7 Restart the un...

Страница 23: ...ration and after shutdown the system will partially drain back into the oil reservoir and the oil level may read higher than when operating on load DO NOT DRAIN OIL TO CORRECT on the next loaded cycle...

Страница 24: ...SURE ON THE COMPRESSOR NAMEPLATE See Operational Settings in the Controller Operating and Service Manual 9 Operating Mode Refer to Section 4 for detailed information on the control system 10 Enclosure...

Страница 25: ...rm up period is required If the unit is a water cooled heat exchanger model open any manual water inlet valves wide open Start the unit by pushing RUN DAILY CHECK Refer to Section 8 Maintenance Schedu...

Страница 26: ...and operating mode and start the compressor Logging In Before making any changes to the settings on the controller you must log in with an appropriate access level The current access level is indicat...

Страница 27: ...ns Factory Contact Gardner Denver Full access to all settings and features The password rotates automatically throughout the life of the machine It may not be changed This password should only be requ...

Страница 28: ...he Settings Configuration menu as shown in Figure 3 3 Figure 3 3 Configuration Menu First ensure that the units are set as desired by selecting the Locale link from the Configuration menu The Pressure...

Страница 29: ...mezone properly ensures that daylight savings time adjustments will be accounted for automatically The Date and Time Configuration screen is shown in Figure 3 5 Figure 3 5 Date and Time Configuration...

Страница 30: ...gs of the machine are acceptable for most installations However if the Pressure Band displayed on the gauge on the Home screen does not match the desired pressure range for the site the Pressure Band...

Страница 31: ...d maximum values that will be allowed for each box will change dynamically based on the design pressure of the machine as well as the values of the other settings For example to increase the Load pres...

Страница 32: ...ge Status Bar on the Home screen or by navigating to Alarms Active Alarms through the Menu The Active Alarms screen is shown in Figure 3 9 Figure 3 9 Active Alarms Screen If the alarm icon in the Alar...

Страница 33: ...wn as shown You will need to jog both individually to verify correct rotation The Jog Delay field allows you to delay the start of the jog from the time that you press the Start Jog button This is to...

Страница 34: ...ee to the Wiring Diagrams listed by voltage at the end of this section for more details on the location of the referredhardware Governor Controller The compressor package features the Governor Control...

Страница 35: ...oil reservoir outlet ahead of the minimum pressure valve When the solenoid is de energized the valve opens and the coolant system is blown down When the solenoid is energized the valve closes to allow...

Страница 36: ...pproximately 65 psig in the oil reservoir When the air pressure on the upstream reservoir side of the valve rises above 65 psig the spring is overridden and the valve opens to full porting The valve d...

Страница 37: ...both valves de energized the normally open IVC valve allows control pressure to the inlet piston to close the valve If IVC only is energized the inlet valve is held in its current position If both val...

Страница 38: ...st be clean and free of burrs and scale Take care not to scrape the cylinder walls when moving the pistons Solenoid Valves TVC and TVO Electra Saver only These valves control the position of the turn...

Страница 39: ...ensor is located near the separator and is used to monitor temperature and shut down the compressor if high temperatures are detected Emergency Stop Push Button This is a maintained push button and re...

Страница 40: ...ntrol and overload protection for the main drive motor Wiring diagrams for typical Wye Delta applications are illustrated on pages 43 thru 50 Overload protection is provided for each motor on voltage...

Страница 41: ...13 21 616 v00 Page 40 FIGURE 4 6 COMPRESSOR PACKAGE P ID 300EBF797 EB Ref Drawing...

Страница 42: ...On On A D D Open Increasing Open TV Modulate Closed Off Closed On Open On Closed Off Closed On On A D D Open Decreasing Open IV Modulate Open On Closed On Closed Off Closed Off Closed On On A D D Ope...

Страница 43: ...efore doing any service or diagnostics on the electrical system FIGURE 4 8 ELECTRA SAVER II WIRING DIAGRAMS WIRING DIAGRAM HP VOLTAGE STARTER 311EBG546 125 575 3 60 YES 150 200 313EBG546 125 380 3 50...

Страница 44: ...13 21 616 v00 Page 43 313EBG546 06 Ref Drawing Page 2 of 14 FIGURE 4 9 WIRING DIAGRAM WYE DELTA AIR COOLED WATER COOLED 125 200 HP 460 VOLT...

Страница 45: ...13 21 616 v00 Page 44 313EBG546 06 Ref Drawing Page 3 of 14 FIGURE 4 10 WIRING DIAGRAM WYE DELTA AIR COOLED WATER COOLED 125 200 HP 460 VOLT...

Страница 46: ...13 21 616 v00 Page 45 313EBG546 06 Ref Drawing Page 4 of 14 FIGURE 4 11 WIRING DIAGRAM WYE DELTA AIR COOLED WATER COOLED 125 200 HP 460 VOLT...

Страница 47: ...13 21 616 v00 Page 46 313EBG546 06 Ref Drawing Page 5 of 14 FIGURE 4 12 WIRING DIAGRAM WYE DELTA AIR COOLED WATER COOLED 125 200 HP 460 VOLT...

Страница 48: ...13 WIRING DIAGRAM WYE DELTA AIR COOLED WATER COOLED 125 200 HP 460 VOLT FIGURE 4 14 WIRING DIAGRAM WYE DELTA AIR COOLED WATER COOLED 125 200 HP 460 VOLT 313EBFG46 06 Ref Drawing Page 6 of 14 313EBG54...

Страница 49: ...13 21 616 v00 Page 48 313EBG546 06 Ref Drawing Page 8 of 14 FIGURE 4 15 WIRING DIAGRAM WYE DELTA AIR COOLED WATER COOLED 125 200 HP 460 VOLT...

Страница 50: ...13 21 616 v00 Page 49 313EBG546 06 Ref Drawing Pages 9 of 14 FIGURE 4 16 WIRING DIAGRAM WYE DELTA AIR COOLED WATER COOLED 125 200 HP 460 VOLT...

Страница 51: ...06 Ref Drawing Pages 10 of 14 313EBG546 06 Ref Drawing Pages 11 of 14 FIGURE 4 17 WIRING DIAGRAM WYE DELTA AIR COOLED WATER COOLED 125 200 HP 460 VOLT FIGURE 4 18 WIRING DIAGRAM WYE DELTA AIR COOLED W...

Страница 52: ...NDED LUBRICANT Gardner Denver compressors are factory filled with AEON lubricants These lubricants are formulated to the highest quality standards and are factory authorized tested and approved for us...

Страница 53: ...ure that it is operating properly The best method for detecting moisture is a disciplined lubricant sampling analysis program every 2 000 hours of operation If moisture is observed in the oil reservoi...

Страница 54: ...is of the chart and then reading the appropriate pressure curve to determine the corresponding dew point temperature on the left axis of the chart The compressor discharge temperature must be maintain...

Страница 55: ...13 21 616 v00 Page 54 300EBF797 EB Ref Drawing Figure 5 3 FLOW DIAGRAM AIR OIL SYSTEM...

Страница 56: ...13 21 616 v00 Page 55 301EBG797 00 Ref Drawing Figure 5 4 OIL FLOW DIAGRAM REMOTE MOUNTED COOLER...

Страница 57: ...sealant on all steel to aluminum threaded connections All piping should be firmly supported to avoid strain on the cooler manifold and connections Flexible connections should be installed in all inte...

Страница 58: ...This will shut the oil stop valve and prevent excessive oil from running into the reservoir Failure to install these parts or installations with pipe lengths and or vertical runs outside the recommend...

Страница 59: ...f the fill range is shown in Figure 5 5 page 59 Repeated addition of oil between oil changes may indicate excessive oil carry over and should be investigated LUBRICANT CHANGE PROCEDURE Following are t...

Страница 60: ...EVEL GAUGE Figure 1 6 page 11 and Figure 5 5 indicates the amount of oil in the oil reservoir Read oil level only when unit is on In operation the oil level will fluctuate as the compressor loads and...

Страница 61: ...9000SP Change Interval Up to 180 F 82 C 4000 hrs 8000 hrs 180 F to 190 F 82 C to 88 C 3000 hrs 6000 hrs 190 F to 200 F 88 C to 93 C 2000 hrs 4000 hrs 200 F 93 C 1000 hrs 2000 hrs Figure 5 6 OIL CHANG...

Страница 62: ...the drain valve to a suitable container or sump 3 If the drained oil and or the oil filter element are contaminated with dirt flush the entire system reservoir oil cooler mixing valve and lines Inspe...

Страница 63: ...RRECT On the next start oil will again fill the system and the gauge will indicate operating at the proper level DO NOT OVERFILL as oil carryover will result The quantity of oil required to raise the...

Страница 64: ...the gasket face of the filter body 4 Coat the new element gasket with clean lubricant used in the unit 5 Screw the new element on the filter body and tighten by hand DO NOT OVER TIGHTEN THE ELEMENT 6...

Страница 65: ...mix with oil from the bypass After the unit is warmed up the mixing valve maintains oil injection temperature into the compressor at a minimum of 130 F 55 C or 160 F 71 C depending on the air end Thi...

Страница 66: ...one or more of these conditions exist may result in increased maintenance and operation expense reduced equipment life and emergency shutdown It is strongly recommended that a reputable local water t...

Страница 67: ...ing screw is an index line for use with the index scale 0 to 8 in obtaining a desired setting These valves must be handled with care and proper tools and techniques must be used when working on the va...

Страница 68: ...ation 303EBD797 Ref Drawing Figure 5 12 OIL SEPARATOR COMPRESSOR GD ELIMINATOR OIL SEPARATOR located in a separate housing consists of a renewable cartridge type separator element and provides the fin...

Страница 69: ...e condition of the separator can be determined by pressure differential gauging or by inspection Pressure Differential Gauging The CHANGE SEPARATOR advisory will occur when the pressure differential a...

Страница 70: ...K The following readings are based on ambient temperature of 80 F 27 C for air cooled oil cooler and 80 F 27 C inlet water on water cooled oil cooler with the system in good condition Compressor shoul...

Страница 71: ...et temperature is approximately the same as air discharge temperature see the gauge on the instrument panel The outlet oil temperature may be checked by installing a tee at the oil filter outlet Oil C...

Страница 72: ...element cylinder and lift off the air filter element cylinder and shroud The shroud can be removed for easier handling of the filter assembly by removing the wingnut on top of the shroud and lifting...

Страница 73: ...would indicate a rupture or crack in the filter element Inlet Tube Inspect the inlet tube for dirt accumulation each time the filter is serviced Clean the tube when required by ramming a clean dry clo...

Страница 74: ...ted by a resilient type flexible coupling with a single cushion The coupling does not require lubrication If maintenance on mating parts is required reassemble coupling as follows Rotating machinery c...

Страница 75: ...7 1 69 in 40 43mm A smaller gap will produce abnormal wear of the element by friction and excessive thermal expansion the latter could cause compressor damage by axially displacing the input shaft Mak...

Страница 76: ...he coupling the same direction as the rotation arrow on the airend Incorrect rotation will greatly decrease the torque carrying capacity of the coupling Rotating machinery can cause personal injury or...

Страница 77: ...essed air carrying a nonflammable safety solvent that will not damage aluminum in a direction opposite that of the cooling air flow The cleaning operation will keep the exterior cooling surfaces clean...

Страница 78: ...x x x x x x Replace air filter element x x x x x x x x x x x Oil Sample x x x x x x x x x x Replace Air Oil Separator x x x x x x Inspect clean if necessary scavenge line replace check x x x x x Insp...

Страница 79: ...x x Replace air filter element x x x x x x x x x x Oil Sample x x x x x x x x x x Replace Air Oil Separator x x x x x Inspect clean if necessary scavenge line replace check x x x x x Inspect service i...

Страница 80: ...on 2 Blown fuse in starter 2 Replace fuse investigate control box if fuses continue to blow 3 Motor starter overload 3 Reset and investigate heaters trips cause of overload Compressor does not unload...

Страница 81: ...leaks found 5 Aftercooler is frozen 5 Thaw out This machine cannot operate in temperatures below 32 F 0 C 6 Unload pressure adjusted 6 Adjust the unload too low pressure Excessive oil consumption 1 O...

Страница 82: ...re valve 7 Operation at elevated discharge temperatures 8 Scavenge line check valve failure 5 Use Gardner Denver AEON lubricating coolants 6 Replace seals in valve 7 Reduce temperature See High Discha...

Страница 83: ...ervice personnel for repair or replacement of any product or part which in the Company s sole judgment is proved not to be as warranted Labor shall be limited to the amount specified in the Company s...

Страница 84: ...For additional information contact your local representative or visit www contactgd com compressors 2020 Gardner Denver Inc Printed in U S A...

Отзывы: