13-10-615 Page 14
Figure 2-1 – TYPICAL COMPRESSOR ROOM
Minimum Air Flow * for Compression
and Cooling – CFM
(M
3
/MIN)
HP
(Kw)
Air-Cooled
Package
Air-Cooled
Module
Water-Cooled
Package
200 (150)
28,500 (808)
20,500 (580)
8,000 (226)
250 (186)
35,900 (1016)
26,000 (736)
9,900 (280)
300 (225)
37,900 (1073)
26,000 (736)
11,000 (311)
* 80
°
F (27
°
C) Inlet Air
Figure 2-2 – AIR FLOW CHART
Air-Cooled Units
- A combination oil/aftercooler is supplied as standard equipment on all air-cooled
units. The air-cooled unit with the standard enclosure requires sufficient flow, Figure 2-2, for the
compressor oil/aftercooling system and for electric motor cooling. Air is drawn into the unit at the motor
side of the enclosure and is exhausted at the oil cooler side. Do not block the air flow to and from the
unit. Allow three and one-half (3-1/2) feet (1.1 m) to the nearest obstruction on the starter end and control
box end of the unit. Allow three (3) feet (.9 m) to the nearest obstruction above and on other sides of unit.
For continuous efficiency, oil cooler cores must be periodically cleaned with either vacuum or compressed
air. If wet cleaning is required, shield motor and spray on a mild soap solution and flush with clean water.
Water-Cooled Units
- The water-cooled unit with the standard enclosure requires sufficient air flow,
Figure 2-2, for electric motor cooling. Air is drawn into the unit at the top of the enclosure and is
exhausted at the motor side. Do not block air flow to and from unit. Allow three and one-half (3-1/2) feet
(1.1 m) to the nearest obstruction on the starter end and control box side of the unit. Allow three (3) feet
(.9 m) to the nearest obstruction above and on other sides of the unit.
Содержание AUTO SENTRY EAU99P
Страница 13: ...13 10 615 Page 12 Figure 1 6 PACKAGE AIR OIL FLOW DIAGRAM 202EDM797 Ref Drawing ...
Страница 35: ...13 10 615 Page 34 Figure 4 7 CONTROL SCHEMATIC COMPRESSOR AT FULL LOAD 206EAU797 B Ref Drawing ...
Страница 38: ...13 10 615 Page 37 Figure 4 10 WIRING DIAGRAM WYE DELTA ES CONTROLLER AIR COOLED 202EAU546 D Ref Drawing ...
Страница 40: ...13 10 615 Page 39 205EAU546 D Ref Drawing Page 2 of 2 ...
Страница 44: ...13 10 615 Page 43 Figure 5 3 FLOW DIAGRAM 210EAU797 B Ref Drawing ...