ZNS Installation and Operation Manual

Issue 4 12/4/98

2

COMMON CARD

Indicators

The ZNS common card module has one LED. When first powered it flashes the
version number of the firmware on the ZNS module. Thereafter it will flash
whenever it is responding with zone information to an INS-2 poll.

Default Operation

Default operation is a mode that allows alarms to be sensed and automatically routed
to the Signaling Circuits, if for some reason the ZNS controller fails.

Auxiliary Power

Auxiliary power is available on the Common Card from terminals A+, A-. Resetable
smoke detector power is available from terminals S+, S-. This power is removed for
four seconds when the system is reset. Combined total current available from both
A+,A- and S+,S- is 0.5 amps.

Programming

The ZNS Common Card is enabled by accessing level 4 programming area of the
INS-2 main board. Press the F1 key until the LED above the F1 key is illuminated.

Output controller location C220 must also be enabled and cannot be used by any
other devices. This output controller location allows the ZNS common card to reset
the S+, S- output.

ZONE CARD

Indicators

Each 2 zone module has two LED’s per zone, one to indicate alarm and the other to
indicate trouble.  The standard zone module has a red and yellow, the supervisory
zone has two yellow LED’s.

Alarm Disconnect

Each zone of the 31016 2 zone card has a disconnect switch located next to the
LEDs. When this switch is activated, the zone will not report an Alarm, but it will
show that it is in Trouble

Low /High Current
Operation

Each zone of the 31016 2 zone card can be programmed for two modes of operation,
low current and high current. The module is factory set as a high current zone. Low
current mode is selected by removing the following resistors.

Odd Zone

Even Zone

Resistors to remove for low current operation.           R1,R2,R3          R21,R22,R23

The EOL resistor high current value is 4.7K ohms and the low current value is 15K
ohms.

NOTE:

 Low Current zones will not function with 2-wire Smoke Detectors, and

should be used with contact closure devices only.

Addressing

The 31016 zone modules must be mounted from left to right. If a slot is empty the
system will not detect  modules beyond the first open slot.

Zone Programming

Each 31016 2 zone card has jumpers to distinguish between Class A or Class B
initiating circuits. There are also jumpers to program latching and non-latching
zones. All 31016 modules are factory set for Class B latching alarm operation. See
the chart below for programming options. Refer to drawing A-M1105 For resistor
locations.

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Содержание ZNS

Страница 1: ...AL FIRE ALARM CONTROL PANEL Installation Operation Manual The Gamewell Company 60 Pleasant Street Part No 71774 Ashland MA 01721 Issue 4 12 4 98 PROPRIETARY MATERIAL Technical Manuals Online http www...

Страница 2: ...The Gamewell Company Such information and technical drawings may not be copied or reproduced in any manner or disclosed to organizations that might be competitive to Gamewell without the express prio...

Страница 3: ...ity To maximize system performance and minimize risk of damage to the equipment we suggest using all Gamewell Components 4 There is no substitute for proper maintenance and testing of this or any life...

Страница 4: ...lt Operation 2 Auxiliary Power 2 Programming 2 Zone Card 2 Indicators 2 Alarm Disconnect 2 Low High Current Operation 2 Addressing 2 Zone Programming 2 Programming 3 Power Requirements 3 Appendix A 4...

Страница 5: ...one modules INSTALLATION AND WIRING Mechanical Two cabinet sizes are available for the ZNS the smaller is used to house a 2 to 16 zone system and the larger is used on 2 to 32 zone systems 21 W x 25 5...

Страница 6: ...e The standard zone module has a red and yellow the supervisory zone has two yellow LED s Alarm Disconnect Each zone of the 31016 2 zone card has a disconnect switch located next to the LEDs When this...

Страница 7: ...nstalled W2A Installed Class A W1A Removed W2A Removed Zone cards are shipped with all jumpers installed Class B Alarms Latched Power Requirements The ZNS common card draws 2 mA from the 24V supply an...

Страница 8: ...No Apollo Part No Qty Gamewell Model No Apollo Part No 71033 55000 350 71036 45681 200 71034 55000 250 71086 45681 220 71035 55000 150 20 71086 LOW 45681 232 71035 160 55000 151 71086 GREEN 45681 231...

Страница 9: ...FW 71741 ET90 2430C FW 71543 AS 2415 VFR 71685 NH 12 24 R 71742 ET90 2475C FW 71544 AS 241575 VFR 71686 NS 2415W FR 71743 ET90 24100C FW 71545 AS 2430 VFR 71687 NS 241575W FR 71744 E70 2415W FR 71546...

Страница 10: ...Drawings D M781 Ass y of ZNS 16 Zones D M780 Ass y of ZNS 32 Zones A M1104 Mounting Instruction Card Guide A M1105 Configuring of 2 Zone Card D W1171 Wiring ZNS System A W544 Wiring ZNS 2 Zone Card Te...

Отзывы: