ZNS Installation and Operation Manual

Issue 4 12/4/98

3

Programming

Programming of the 31016 modules is accomplished with the INS-2 laptop software.
Each zone card installed requires 2 addresses regardless of wether both zones are
being used or not. The 31016 requires no programming of its address. It is addressed
automatically, via the ZNS, by its physical location to the addresses of 1 through 32.
Additional addressable modules may be added to the addressable circuits 1 and 2
starting with address 33.

JUMPER PROGRAMMING

Odd Zone

Even Zone

Alarms Latched

W1L  Installed

W2L  Installed

Alarms Not Latched
(Supervisory Alarms Only)

W1L Removed

W2L Removed

Class B

W1A  Installed

W2A  Installed

Class A

W1A Removed

W2A Removed

Zone cards are shipped with all jumpers installed (Class B, Alarms Latched).

Power Requirements

The ZNS common card draws 2 mA from the +24V supply and 5 mA from the
+5V supply.

The 31015 mother boards do not draw any power from the system.

Each 31016 zone card draws 0.5 mA from the +5V supply plus 6.5 mA for each
trouble or alarm LED on.  Note that for one zone, the trouble and alarm LEDs will
never be on at the same time.

The current draw from the +24V supply for each zone on a 31016 zone card
depends upon whether it is configured for hi-current or low current operation.

lo-current -- without detect

2.5 mA max

lo-current -- in alarm

6 mA max

hi-current -- without detectors

6.5 mA max

hi-current -- with detectors

9.1 mA max

hi-current -- in alarm

60 mA max

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Содержание ZNS

Страница 1: ...AL FIRE ALARM CONTROL PANEL Installation Operation Manual The Gamewell Company 60 Pleasant Street Part No 71774 Ashland MA 01721 Issue 4 12 4 98 PROPRIETARY MATERIAL Technical Manuals Online http www...

Страница 2: ...The Gamewell Company Such information and technical drawings may not be copied or reproduced in any manner or disclosed to organizations that might be competitive to Gamewell without the express prio...

Страница 3: ...ity To maximize system performance and minimize risk of damage to the equipment we suggest using all Gamewell Components 4 There is no substitute for proper maintenance and testing of this or any life...

Страница 4: ...lt Operation 2 Auxiliary Power 2 Programming 2 Zone Card 2 Indicators 2 Alarm Disconnect 2 Low High Current Operation 2 Addressing 2 Zone Programming 2 Programming 3 Power Requirements 3 Appendix A 4...

Страница 5: ...one modules INSTALLATION AND WIRING Mechanical Two cabinet sizes are available for the ZNS the smaller is used to house a 2 to 16 zone system and the larger is used on 2 to 32 zone systems 21 W x 25 5...

Страница 6: ...e The standard zone module has a red and yellow the supervisory zone has two yellow LED s Alarm Disconnect Each zone of the 31016 2 zone card has a disconnect switch located next to the LEDs When this...

Страница 7: ...nstalled W2A Installed Class A W1A Removed W2A Removed Zone cards are shipped with all jumpers installed Class B Alarms Latched Power Requirements The ZNS common card draws 2 mA from the 24V supply an...

Страница 8: ...No Apollo Part No Qty Gamewell Model No Apollo Part No 71033 55000 350 71036 45681 200 71034 55000 250 71086 45681 220 71035 55000 150 20 71086 LOW 45681 232 71035 160 55000 151 71086 GREEN 45681 231...

Страница 9: ...FW 71741 ET90 2430C FW 71543 AS 2415 VFR 71685 NH 12 24 R 71742 ET90 2475C FW 71544 AS 241575 VFR 71686 NS 2415W FR 71743 ET90 24100C FW 71545 AS 2430 VFR 71687 NS 241575W FR 71744 E70 2415W FR 71546...

Страница 10: ...Drawings D M781 Ass y of ZNS 16 Zones D M780 Ass y of ZNS 32 Zones A M1104 Mounting Instruction Card Guide A M1105 Configuring of 2 Zone Card D W1171 Wiring ZNS System A W544 Wiring ZNS 2 Zone Card Te...

Отзывы: