-64-
6.6.4.3
Assign Digital Inputs
•
Choose Cleaning Event 1…2
•
Set Cleaning Frequency in Hours = 0
•
Specify the
Cycle Duration
, and
Purge Time.
Save the settings. Activate the
Relay through Assign Digital Inputs. The Cleaning Cycle gets activated ONLY
ONCE.
Note:
Whenever you are trying to activate a Cleaning Event through
Assign
Digital Inputs
make sure that the Cleaning Frequency in Hours is 0.
Failing to do so may cause malfunctioning of the Cleaning Event.
6.6.4.4
Set Alarms
You can setup Alarm set conditions. Each Alarm can have a
HYSTERESIS
and a
TIME DELAY
(the condition must be met for at least this time before the alarm is
reported). The alarm mode (LOW, HIGH, LOW LATCH, HIGH LATCH) can be
selected per individual Alarm.
Alarms can be assigned to the following signals
Result1
Result2
Result3
Result4
Ambient Temp
General Alarm
The different Alarm Types are
Low
Low Latch
High
High Latch
Choose on the
Alarm
(1- 4)
.
Specify the signal to which the Alarm needs to be assigned by Choosing on the
Assigned Signal
Toggle Button.
Содержание MONITEK MESSENGER
Страница 1: ...MESSENGER PC TRANSMITTER User s manual Release 1 2 September 15 2015...
Страница 11: ...9 Installation dimensions for Messenger PC transmitter in fiberglass enclosure...
Страница 12: ...10 Installation dimensions for Messenger PC transmitter in stainless steel enclosure...
Страница 13: ...11 1 3 2 Transmitter and Sensor Wiring System Layout and Interconnections details...
Страница 14: ...12...
Страница 15: ...13...
Страница 33: ...31 2 6 LCD Display OPTIONAL Contrast Adjust This option is not applicable to the Messenger PC Transmitter...