GALA MIG 3000/3800.
17
2. TRANSPORT AND INSTALLATION
Knocks and sudden movements must be avoided when transporting the equipment. The transport position
will be shown by arrows on the packaging. In any case, the equipment must be kept horizontal and the
packaging protected from water.
GALA MIG 3000/3800 assembly
Once the equipment has been unpacked the wheels must be mounted:
5º
6º
2º
4º
3º
7º
2.1. ELECTRICAL SUPPLY INSTALLATION.
The welding equipment location must satisfy the following requirements:
Place: Dry and ventilated, far enough away from the cutting area in order to prevent the metal dust caused
by the cutting process from getting into the equipment.
Electrical installation. Electrical elements of the installation.
Protection system
GALA MIG
3000
GALA MIG
3800
Connection
plug.
32A 3P + T - 230V
16A 3P + T - 400V
32A 3P + T - 230V
16A 3P + T - 400V
Magnetothermal
switch (Curve
“D”)
3P 20 A - 230V
3P 15 A - 400V
3P 25 A - 230V
3P 20 A - 400V
Differential
switch.
(Minimum)
3P 25A/300 mA
3P 25A/300 mA
DO NOT FORGET TO FIT THE EARTH CONNECTION INTO THE PLUG.