GALaxy eHydro Elevator Controller Section 7
– Main CPU Adjustable Variables
7-11
Table 7-3: Car Options
Field Variable
Min
Max
Initial Units
Invert CLF
0
1
1
-
Invert The Logic For The Car Light Fan.
If set to 0 car
light fan is normally open. If set to 1 car light fan is
normally closed.
Invert LOS
0
1
0
-
Invert Low Oil Switch
(LOS)
Invert LPS
0
1
0
-
Invert Low Pressure Switch
(LPS)
Invert TPL
0
1
0
-
Invert Temperature Low Switch
(TPL)
ISER Outp Ctl
0
7
0
-
Invert In Service Output.
1 = The in service light output is turned off when the
car is in service instead of turned on.
2 = The ISER output will function as an elevator in use
light.
4 = This output functions as out of service from a
shutdown and does not include independent,
inspection or recovery mode.
Lant Pref Dly
0
3
0
sec
Lantern Preference Change Delay.
When the
direction preference for the elevator changes, we
clear the lanterns and wait for this amount of time
before the lanterns are turned on again.
LbyLan NCU/IR
0
1
0
-
Lobby Lantern NCU/IR.
0 = Light the lanterns on IR service at each floor. The
lantern will not light at the lobby if next up operation
is selected because the IR car will not be selected to
be the next up car.
1 = The IR car will light the lantern at all the floors and
the lobby even with the system on next up operation.
Min Door T En
0
1
0
-
Minimum Door Time Enable.
0 = Disabled
1 = The minimum door time for a car call or a hall call
is set from the car or hall call dwell timers and cannot
be shortened by the Door Close button.
Содержание GALaxy eHydro
Страница 50: ...GALaxy eHydro Elevator Controller Section 4 Troubleshooting 4 4 Figure 4 1 Main CPU NTS and Safety PAL System ...
Страница 66: ...GALaxy eHydro Elevator Controller Section 5 LCD Interface 5 2 5 2 LCD Menus 5 2 1 Elevator Status Figure 5 1 ...
Страница 83: ...GALaxy eHydro Elevator Controller Section 5 LCD Interface 5 19 5 2 5 2 Remove Relocation I O Figure 5 16 ...
Страница 87: ...GALaxy eHydro Elevator Controller Section 5 LCD Interface 5 23 5 2 8 1 Group Comm Status Figure 5 20 ...
Страница 88: ...GALaxy eHydro Elevator Controller Section 5 LCD Interface 5 24 5 2 8 2 Group Can Comm Status Figure 5 21 ...
Страница 89: ...GALaxy eHydro Elevator Controller Section 5 LCD Interface 5 25 5 2 8 3 Car Can Comm Status Figure 5 22 ...
Страница 91: ...GALaxy eHydro Elevator Controller Section 5 LCD Interface 5 27 5 2 8 5 SPI Comm Status Figure 5 24 ...