D1020 

- SIL 2 Powered Isolating Driver Smart-Hart compatible 

G.M. International ISM0012-14 

Parameters Table 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Device Parameters 

D1020 Associated 

Apparatus Parameters 

Uo / Voc = 25.2 V 

Ui / Vmax 

In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check 
its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded 
by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D1020 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check 
that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective 
gas group. See parameters on

 

enclosure side and the ones indicated in the table below: 

D1020 Terminals 

Ch1 

Ch2 

14 - 15 

10 - 11 

Io / Isc = 87 mA 

Ch1 

Ch2 

14 - 15 

10 - 11 

Po / Po = 548 mW 

Ch1 

Ch2 

14 - 15 

10 - 11 

 

Ii/ Imax 

 

Pi / Pi 

 

 

For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable), 
then 50 % of Co and Lo parameters are applicable and shall not be exceeded 

(50 % of the Co and Lo become the limits which must include the cable such that 

Ci C cable 

 50 % of Co and Li  L cable 

 50 % of Lo). 

If the cable parameters are unknown, the following value may be used: Capacitance 60pF per foot (180pF per meter), Inductance 0.20µH per foot (0.60µH per meter). 
The Intrinsic Safety Entity Concept allows the interconnection of Intrinsically Safe devices approved with entity parameters not specifically examined in combination as a system when 
the above conditions are respected. 
For Division 1 and Zone 0 installations, the configuration of Intrinsically Safe Equipment must be FM approved under Entity Concept (or third party approved); 
for Division 2 installations, the configuration of Intrinsically Safe Equipment must be FM approved under non-incendive field wiring or Entity Concept (or third party approved). 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Cable Parameters 

D1020 Terminals 

Ch1 

Ch2 

14 - 15 

10 - 11 

D1020 Associated 

Apparatus Parameters 

Ci / Ci  C cable 

 

IIC (A, B) 

Co / Ca = 105 nF 
Co / Ca = 819 nF 

Co / Ca = 2.899 µF 

IIB (C) 
IIA (D) 

NOTE for USA and Canada: 

IIC equal to Gas Groups A, B, C, D, E, F and G 
IIB equal to Gas Groups C, D, E, F and G 

IIA equal to Gas Groups D, E, F and G 

Co / Ca = 4.15 µF 

Co / Ca = 819 nF 

IIIC 

Ch1 

Ch2 

14 - 15 

10 - 11 

Li / Li L cable 

 

IIC (A, B) 

Lo / La = 4.6 mH 

Lo / La = 18.7 mH 
Lo / La = 37.5 mH 

IIB (C) 
IIA (D) 

Lo / La = 61.5 mH 
Lo / La = 18.7 mH 

IIIC 

Ch1 

Ch2 

14 - 15 

10 - 11 

Li / Ri device and 

L cable / R cable 

 

IIC (A, B) 

Lo / Ro = 64.9 µH/

 

Lo / Ro = 259.6 µH/

 

Lo / Ro = 519.3 µH/

 

IIB (C) 
IIA (D) 

Lo / Ro = 851.9 µH/

 

Lo / Ro = 259.6 µH/

 

IIIC 

Содержание D1020D

Страница 1: ...D1020 SIL 2 Powered Isolating Driver Smart Hart compatible ISM0012 14 D1020S D1020D INSTRUCTION SAFETY MANUAL SIL 2 Powered Isolating Driver Smart Hart compatible DIN Rail Models D1020S D1020D ...

Страница 2: ...tibility CE mark compliant conforms to Directive 2014 34 EU ATEX 2014 30 EU EMC 2014 35 EU LVD 2011 65 EU RoHS Environmental conditions Operating temperature limits 20 to 60 C relative humidity max 95 Storage temperature limits 45 to 80 C Safety Description ATEX II 1 G Ex ia Ga IIC II 1 D Ex ia Da IIIC I M1 Ex ia Ma I II 3G Ex nA IIC T4 Gc IECEx INMETRO Ex ia Ga IIC Ex ia Da IIIC Ex ia Ma I Ex nA ...

Страница 3: ...ations High Reliability SMD components High Density two channels per unit Simplified installation using standard DIN Rail and plug in terminal blocks 250 Vrms Um max voltage allowed to the instruments associated with the barrier Not used Terminal block connections HAZARDOUS AREA SAFE AREA Output Ch 2 for I P Converter Output Ch 2 for I P Converter Not used Not used Output Ch 1 for I P Converter Ou...

Страница 4: ...nd shall not be exceeded 50 of the Co and Lo become the limits which must include the cable such that Ci device C cable 50 of Co and Li device L cable 50 of Lo If the cable parameters are unknown the following value may be used Capacitance 60pF per foot 180pF per meter Inductance 0 20µH per foot 0 60µH per meter The Intrinsic Safety Entity Concept allows the interconnection of Intrinsically Safe d...

Страница 5: ...F G CLASS III DIVISION 1 CLASS I ZONE 0 GROUP IIC SAFE AREA ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1020S 14 15 3 4 1 2 HHT Supply 24 Vdc Source I In 1 HHT I P Out 1 I P Converter MODEL D1020D 14 15 3 4 1 2 HHT Ch1 Supply 24 Vdc Source I In 1 HHT I P Out 1 10 11 5 6 Source I HHT HHT I P I P Converter I P Converter I...

Страница 6: ...fined Fail Safe state or deviates the output current by more than 5 full span 0 8 mA Fail High failure mode that causes the output signal to go above the maximum output current 20 mA This failure mode is considered as a Dangerous Undetected failure Fail Low failure mode that causes the output signal to go below the minimum output current 4 mA This failure mode is considered as a Safe Undetected fa...

Страница 7: ...I Division 2 or Class I Zone 2 location the wiring between the control equipment and the D1020 associated apparatus shall be accomplished via conduit connections or another acceptable Division 2 Zone 2 wiring method according to the NEC and the CEC Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground D1020 series must be installed o...

Страница 8: ...tive and 15 for negative For Model D1020D in addition to channel 1 connections above connect terminal 10 for positive and 11 for negative on channel 2 Intrinsically Safe conductors must be identified and segregated from non I S and wired in accordance to the relevant national international installation standards e g EN IEC60079 14 Electrical apparatus for explosive gas atmospheres Part 14 Electric...

Страница 9: ...deviation presented in the section Technical Data Set calibrator CAL at 20 000 mA and verify that the output current read by multimeter DMM is correspondent with a maximum deviation presented in the section Technical Data Set calibrator CAL at 20 000 mA and power supply PS at 20 0 V verify that multimeter V1 reads input voltage as presented in the section Technical Data If the maximum deviation is...

Отзывы: