- SIL 2 Powered Isolating Driver Smart-Hart compatible 

G.M. International ISM0012-14 

General Description: 

The single and dual channel DIN Rail Isolating Driver, D1020S and D1020D, isolates and transfers a 4-20, 0-20 mA signal from a controller located in Safe Area 

to a load of up to 750 

 in Hazardous Area. It has a high output capacity of 15 V at 20 mA combined with a low drop across its input terminals. The circuit allows bi-directional 

communication signals, for Smart I/P. In the 4-20 mA input range, a field open circuit reflects a high impedance to the control device output circuit. 

Function: 

1 or 2 channels I.S. mA analog output for 2 wire I/P Smart converters or valve positioners, provides 3 port isolation (input/output/supply). 

Signalling LED: 

Power supply indication (green). 

Smart Communication Frequency Band: 

0.5 to 40 KHz within 3 dB (Hart and higher frequency protocols). 

EMC: 

Fully compliant with CE marking applicable requirements. 

Functional Safety Management Certification: 

G.M. International is certified by TUV to conform to IEC61508:2010  

part 1 clauses 5-6 for safety related systems up to and included SIL3. 

 

 

Supply: 

24 Vdc nom (20 to 30 Vdc) reverse polarity protected, ripple within voltage limits 

 5 Vpp. 

Current consumption @ 24 V:

 95 mA for 2 channels D1020D, 50 mA for 1 channel D1020S with 20 mA output typical. 

Power dissipation:

 1.9 W for 2 channels D1020D, 1.0 W for 1 channel D1020S with 24 V supply voltage and 20 mA output typical. 

Max. power consumption:

 at 30 V supply voltage and overload condition, 2.7 W for 2 channels D1020D, 1.4 W for 1 channel D1020S. 

Isolation (Test Voltage): 

I.S. Out/In 1.5 KV; I.S. Out/Supply 1.5 KV; I.S. Out/I.S. Out 500 V; In/Supply 500 V; In/In 500 V. 

Input: 

0/4 to 20 mA with 

 2.0 V voltage drop, reverse polarity protected. 

Output: 

0/4 to 20 mA, on max. 750 

 load, current limited at 

 23 mA. 

Response time:

 50 ms (10 to 90 % step change). 

Output ripple:

 

 20 mVrms on 250 

 communication load on 0.5 to 40 KHz band. 

Frequency response:

 0.5 to 40 KHz bidirectional within 3 dB (Hart and higher frequency protocols). 

Performance: 

Ref. Conditions 24 V supply, 250 

 load, 23 ± 1 °C ambient temperature. 

Calibration accuracy: 

 ± 0.1 % of full scale. 

Linearity error: 

 ± 0.05 % of full scale. 

Supply voltage influence: 

 ± 0.05 % of full scale for a min to max supply change. 

Load influence:

 

 ± 0.05 % of full scale for a 0 to 100 % load resistance change. 

Temperature influence:

 

 ± 0.01 % on zero and span for a 1 °C change. 

Compatibility: 

 

CE mark compliant, conforms to Directive: 2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS. 

Environmental conditions:  
 

Operating:

 temperature limits -20 to + 60 °C, relative humidity max 95 % . 

Storage:

 temperature limits – 45 to + 80 °C. 

Safety Description: 

ATEX:

 

II (1)G [Ex ia Ga] IIC, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I; II 3G Ex nA IIC T4 Gc 

IECEx / INMETRO:

 [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I; Ex nA IIC T4 Gc 

UL:

 NI / I / 2 / ABCD / T4, AIS / I, II, III / 1 / ABCDEFG, AEx nC [ia] IIC 

C-UL:

 NI / I / 2 / ABCD / T4, AIS / I, II, III / 1 / ABCDEFG, Ex nC [ia] IIC  

FM:

 NI / I / 2 / ABCD / T4, NI / I / 2 / IIC / T4, AIS / I, II, III / 1 / ABCDEFG, AEx [ia] IIC 

FM-C:

 NI / I / 2 / ABCD / T4, NI / I / 2 / IIC / T4, AIS / I, II, III / 1 / ABCDEFG, Ex [ia] IIC 

EAC-EX:

 2Ex nA [ia Ga] IIC T4 Gc X, [Ex ia Da] IIIC X, [Ex ia Ma] I X 

UKR TR n. 898:

 2ExnAiaIICT4 X, ExiaI X 

associated apparatus and non-sparking electrical equipment. 
Uo/Voc = 25.2 V, Io/Isc = 87 mA, Po/Po = 548 mW at terminals 14-15, 10-11. 
Um = 250 Vrms, -20 °C 

 Ta 

 60 °C. 

Approvals: 

DMT 01 ATEX E 042 X conforms to EN60079-0, EN60079-11, EN60079-26. 
IECEx BVS 07.0027X conforms to IEC60079-0, IEC60079-11, IEC60079-26. 
IMQ 09 ATEX 013 X conforms to EN60079-0, EN60079-15. 
IECEx IMQ 13.0011X conforms to IEC60079-0, IEC60079-15. 
INMETRO DNV 13.0108 X conforms to ABNT NBR IEC60079-0, ABNT NBR IEC60079-11, ABNT NBR IEC60079-15, ABNT NBR IEC60079-26, ABNT NBR IEC 61241-11. 
UL & C-UL E222308 conforms to UL913, UL 60079-0, UL60079-11, UL60079-15, 
ANSI/ISA 12.12.01 for UL and CSA-C22.2 No.157-92, CSA-E60079-0, CSA-E60079-11, CSA-C22.2 No. 213 and CSA-E60079-15 for C-UL. 
FM & FM-C No. 3024643, 3029921C, conforms to Class 3600, 3610, 3611, 3810,  
ANSI/ISA 12.12.02, ANSI/ISA 60079-0, ANSI/ISA 60079-11, C22.2 No.142,  
C22.2 No.157, C22.2 No.213, E60079-0, E60079-11, E60079-15. 
C-IT.MH04.B.00306 conforms to GOST R IEC 60079-0,GOST R IEC 60079-11, GOST R IEC 60079-15. 
C

Ц

 16.0034 X conforms to 

ДСТУ

 7113, 

ГОСТ

 22782.5-78, 

ДСТУ

 I

ЕС

 60079-15. 

TÜV Certificate No. C-IS-236198-03, SIL 2 conforms to IEC61508:2010 Ed.2. 
TÜV Certificate No. C-IS-236198-09, SIL 3  Functional Safety Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety. 
DNV No.A-13778 and KR No.MIL20769-EL001 Certificates for maritime applications. 

Mounting: 

T35 DIN Rail according to EN50022. 

Weight:

 about 180 g D1020D, 120 g D1020S. 

Connection:

 by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm

2

Location:

 Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA 

T4 installation. 

Protection class:

 IP 20.  

Dimensions:

 Width 22.5 mm, Depth 99 mm, Height 114.5 mm. 

 

Technical Data 

Characteristics 

FSM

SIL 3

Содержание D1020D

Страница 1: ...D1020 SIL 2 Powered Isolating Driver Smart Hart compatible ISM0012 14 D1020S D1020D INSTRUCTION SAFETY MANUAL SIL 2 Powered Isolating Driver Smart Hart compatible DIN Rail Models D1020S D1020D ...

Страница 2: ...tibility CE mark compliant conforms to Directive 2014 34 EU ATEX 2014 30 EU EMC 2014 35 EU LVD 2011 65 EU RoHS Environmental conditions Operating temperature limits 20 to 60 C relative humidity max 95 Storage temperature limits 45 to 80 C Safety Description ATEX II 1 G Ex ia Ga IIC II 1 D Ex ia Da IIIC I M1 Ex ia Ma I II 3G Ex nA IIC T4 Gc IECEx INMETRO Ex ia Ga IIC Ex ia Da IIIC Ex ia Ma I Ex nA ...

Страница 3: ...ations High Reliability SMD components High Density two channels per unit Simplified installation using standard DIN Rail and plug in terminal blocks 250 Vrms Um max voltage allowed to the instruments associated with the barrier Not used Terminal block connections HAZARDOUS AREA SAFE AREA Output Ch 2 for I P Converter Output Ch 2 for I P Converter Not used Not used Output Ch 1 for I P Converter Ou...

Страница 4: ...nd shall not be exceeded 50 of the Co and Lo become the limits which must include the cable such that Ci device C cable 50 of Co and Li device L cable 50 of Lo If the cable parameters are unknown the following value may be used Capacitance 60pF per foot 180pF per meter Inductance 0 20µH per foot 0 60µH per meter The Intrinsic Safety Entity Concept allows the interconnection of Intrinsically Safe d...

Страница 5: ...F G CLASS III DIVISION 1 CLASS I ZONE 0 GROUP IIC SAFE AREA ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1020S 14 15 3 4 1 2 HHT Supply 24 Vdc Source I In 1 HHT I P Out 1 I P Converter MODEL D1020D 14 15 3 4 1 2 HHT Ch1 Supply 24 Vdc Source I In 1 HHT I P Out 1 10 11 5 6 Source I HHT HHT I P I P Converter I P Converter I...

Страница 6: ...fined Fail Safe state or deviates the output current by more than 5 full span 0 8 mA Fail High failure mode that causes the output signal to go above the maximum output current 20 mA This failure mode is considered as a Dangerous Undetected failure Fail Low failure mode that causes the output signal to go below the minimum output current 4 mA This failure mode is considered as a Safe Undetected fa...

Страница 7: ...I Division 2 or Class I Zone 2 location the wiring between the control equipment and the D1020 associated apparatus shall be accomplished via conduit connections or another acceptable Division 2 Zone 2 wiring method according to the NEC and the CEC Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground D1020 series must be installed o...

Страница 8: ...tive and 15 for negative For Model D1020D in addition to channel 1 connections above connect terminal 10 for positive and 11 for negative on channel 2 Intrinsically Safe conductors must be identified and segregated from non I S and wired in accordance to the relevant national international installation standards e g EN IEC60079 14 Electrical apparatus for explosive gas atmospheres Part 14 Electric...

Страница 9: ...deviation presented in the section Technical Data Set calibrator CAL at 20 000 mA and verify that the output current read by multimeter DMM is correspondent with a maximum deviation presented in the section Technical Data Set calibrator CAL at 20 000 mA and power supply PS at 20 0 V verify that multimeter V1 reads input voltage as presented in the section Technical Data If the maximum deviation is...