MCT-MC
4.3
FDC MCT-MC
- 38 -
Configuring the MCT-MC
4.4 Functions
The MC functions are accessed from the Startup menu and allow the user or OEM to select which screens/menu
items will be enabled (shown) in the runtime application. These functions can be used to customize the system
to meet specific requirements.
When functions are disabled at the Configurator level from the functions list, it will be disabled in the runtime
software by removing the menu item or disabling the field so the operator can not select the function or edit any
corresponding settings related to the function. The following list provides the available MC functions, where to
find the menu item(s) applicable to the function and a description of what it applies to.
IMPORTANT:
Disabling functions that are not required for the application results in a system that is clean and
easy to use for the operator; however, be careful when disabling certain items. Without access
to them, there may be no way to determine if the system is operating as required.
MC Function
Runtime Menu Location
Description
Loop View
View\Loop
View loop PV, %Out, set loop set point and set fixed
percentage of output
NOTE:
Without access to the loop view screen, the user
will be unable to set a fixed percentage of output for the
loop. If access to All View is also removed, user will be
unable to turn manual event outputs on and off.
All View
View\Overview
view loop PV, %Out, set loop set point
NOTE:
If access to the Loop View is also removed, the
user will be unable to monitor or adjust loop operation.
Chart View
View\Chart
view and set up real time trends for loops and monitors
Alarm View
View\Alarm
Notifications
view and reset current alarms
current alarm status
NOTE:
With the function disabled, the user will only be
able to access the alarm screen to reset an alarm when
the alarm occurs by pressing the flashing alarm icon.
If the alarm is latching and does not reset, the user will
be unable to return to the screen to try and clear the
alarm unless another alarm occurs to again display the
flashing alarm icon.
Alarm Log
View\Alarm File
view and email alarm history files
Содержание MCT-MC 4.3
Страница 1: ...MCT MC 4 3 User Manual MCT MC 4 3 User Manual Rev A February 2018...
Страница 175: ...MCT MC4 3 Appendix 175 FDC MCT MC A 5 Power Supply Specifications DIN Rail Mount Power Supply Specifications...
Страница 176: ...MCT MC4 3 FDC MCT MC 176 Appendix...
Страница 177: ...MCT MC4 3 Appendix 177 FDC MCT MC Open Frame Power Supply Specifications...
Страница 178: ...MCT MC4 3 FDC MCT MC 178 Appendix...
Страница 179: ...MCT MC4 3 Appendix 179 FDC MCT MC A 6 Power On Delay Relay Specifications GE1A C10HA110...
Страница 180: ...MCT MC4 3 FDC MCT MC 180 Appendix...