![Future Design MCT-MC 4.3 Скачать руководство пользователя страница 158](http://html1.mh-extra.com/html/future-design/mct-mc-4-3/mct-mc-4-3_user-manual_2352024158.webp)
MCT-MC
4.3
FDC MCT-MC
- 158 -
Appendix
*B3
Parameter
Value
Description
0
Program Run
1
Program Hold
2
Static Mode
3
Automatic Tune
5
Manual Mode
*B4
Parameter
Value
Description
Bit0
Event 1 (output 2)
Bit1
Event 2 (output 3)
Bit2
Event 3 (output 4)
Bit3 – Bit15
Not Assigned
*B5
Parameter
Value
Description
Bit0
Automatic Program Run Mode
Bit1
Automatic Program Hold Mode
Bit2
Static Mode
Bit3
Auto Tune Mode
Bit4
Manual Mode
Bit5
Off Mode
Bit6
Failure Transfer
Bit7
Automatic Program Ramp Up
Bit8
Automatic Program Ramp Down
Bit9
Automatic Program Soak
Bit10
Alarm 1 Active
Bit11
Alarm 2 Active
Bit12
Alarm 3 Active
Bit13
Event 1 On
Bit14
Event 2 On
Bit15
Event 3 On
Note:
The events provided by the MC are a combination of all events
provided by all loop controls combined. In order to turn events on and
off, the events assigned to each specific control must be accessed. The
proper event bits must be turned on in each corresponding loop control.
The first event in the MC may actually be output 3 of loop control number
2. This requires bit 1 of the event register to be set on loop control 2 of
the MC.
Note:
Auto tune may not be available depending upon the loop
configuration. If auto tune operation is not available, the loop controller
will revert back to static mode. When auto tune operation completes
normally, the loop controller will revert back to static mode.
Only one mode can be set at time. The program hold mode can not be
set unless a program is currently running. The program mode can then
be switched between run and hold by setting a value of 0 or 1 to the
operation mode register.
When the loop control is in manual mode, the output percentage values
for output 1 (MV1) and output 2 (MV2) can be set by writing to the
corresponding output register.
Содержание MCT-MC 4.3
Страница 1: ...MCT MC 4 3 User Manual MCT MC 4 3 User Manual Rev A February 2018...
Страница 175: ...MCT MC4 3 Appendix 175 FDC MCT MC A 5 Power Supply Specifications DIN Rail Mount Power Supply Specifications...
Страница 176: ...MCT MC4 3 FDC MCT MC 176 Appendix...