Wiring
NOTE:
The connection requires a single twisted-pair cable that is daisy-chained from one MC to the next.
When using shielded twisted-pair cable, be sure to ground only one end of the cable, preferably at the
RS232 to RS485 network adapter. Allowing any other portion of the cable shield to come in contact
with ground, or grounding both ends, will cause ground loop currents to flow in that section of the cable
which can cause communication errors.