3.3.5
Access
This page specifies connection ports and addresses which are
used to access the RTU-810 itself.
RTU MODBUS
address
The address which is used to access the RTU-810 via MODBUS-RTU
protocol, either via local serial port(s) or via radio network.
MODBUS IP port
The port number on which the RTU-810 listens to incoming MODBUS/IP
connections (TCP) or data (UDP). A change of the port needs a device restart.
MODBUS IP
Active
Turns the MODBUS/IP function On or Off. A change needs a device restart.
MODBUS IP
protocol
Selects the use of UDP or TCP for the MODBUS/IP access. Default is TCP.
A change needs a device restart.
Webserver port
The port to which the embedded configuration webserver is listening.
Default is port 80, a change needs a device restart.
Internal TFTP
port
The port to which the internal TFTP server is listening. This is needed for
firmware updates, saving and restoring the configuration and for transferring
PicoLogo applications into the RTU-810. Default is port 69, a change needs
a device restart.