3.2.3.4
RTU Master Mode via IP networks (Q2/3 2017)
From firmware version 2.40 on, the communication to the slave radios can be either the
radio network or an IP network. This enables Point-to-(Multi)point connections also via
LAN or WAN IP networks.
For this reason the use of the routing table will be changed to use the SCADA routing
table 1 or 2, like for the serial master modes. The SCADA routing tables with its IP
entry do have the ability to specify an IP address beside the radio slave address.
In the slave configuration a selection for each slave will be added to configure whether
the slave is connected via radio network or via IP network.
If the radio network is used, the radio slave address will be determined from the entry in
the selected SCADA routing table, for this slave address in a second step the associated
radio routing table will be used.
As the SCADA routing table is defaulted to use a 1:1 entries for the radio slave
addresses 1-239, a firmware update to version 2.40 will not break existing
configurations.