3.2.3.1
Master operation
Fails until station
gets offline
This is the number of consecutive communication failures before a station is
tagged offline. When a station goes offline, this is an error state and all
outputs will be deactivated (see 3.2.3 RTU master mode)
Deafult is 10.
T-Timeout to
slaves
This is the T-timeout value which is transmitted to the slaves. After this
seconds without being polled by the master, the slave will set its outputs to
"OFF" state.
0 disables the T-timeout at the slaves.
X-Timeout to
slaves
This is the X-timeout value which is transmitted to the slaves. When the
slave received this number of radio messages with the same radio layer
address without being polled itself it will set its outputs to "OFF" state.
0 disables the X-timeout at the slaves.
Delay after each
station polling
If this value is greater than 0, the RTU-810 will wait this number of seconds
after a station is been polled before polling the next slave.
Delay after polling
cycle completed
If this value is greater than 0, the RTU-810 will wait this number of seconds
after a complete polling round (all slaves polled once) has been completed.
New timeslot ends
cycle delay
If this is set to "On", in time slot operation the start of a new time slot will
break an ongoing cycle delay.
This can be used to poll each slave only once per time slot. It i.e. one time
slot is active per minute, the cycle delay can be set to 70 seconds. After a
completed polling cycle the polling delay starts, but with the start of the next
time slot in the next minute the remaining cycle delay time will be cancelled
and again one polling round will be performed.