3 - OPERATION
© Fulton 2018
3-14
VSRT_IOM_2018-1213
Par. No.
Parameter
Min Value
Max Value
Fulton Setting
Customer
223
Repetition limit pressure switch mini-gas
1
16
1
225
Gas: Pre-purge time
20 s
60 s
30 s
226
Gas: Pre-ignition time
0.2 s
60 min
2 s
227
Gas: Safety time 1 (TSA1)
0.2 s
10 s
5 s
229
Gas: time to respond to pressure faults in TSA1
0.2 s
9.8 s
1.8 s
230
Gas: Interval 1
0.2 s
60 s
5 s
231
Gas: Safety time 2 (TSA2)
0.2 s
10 s
5 s
232
Gas: Interval 2
0.2 s
60 s
2.0 s
233
Gas: Afterburn time
0.2 s
60 s
8 s
234
Gas: Post purge time
0.2 s
108 mi,
15 s
237
Gas pressure switch-max / POC input
0 = deactivated
1 = pressure switch-max
2 = POC
1
2
2
239
Gas: Forced intermittent operation
0 = deactivated
1 = activated
0
1
1
240
Gas: Repetition limit loss of flame
1
2
1
241
Gas: Execution leakage test
0 = no leakage test
1 = leakage test on start up
2 = leakage test on shut down
3 = leakage test on both
0
3
0
242
Gas: Leakage test evacuation time
0.2 s
10s
3 s
243
Gas: Leakage test time atm pressure
0.2 s
60 s
10 s
244
Gas: Leakage test filling time
0.2 s
10s
3 s
245
Gas: Leakage test time gas pressure
0.2 s
60 s
10 s
246
Gas: Waiting time gas shortage
0.2 s
60 s
10 s
400
Ratio Curves
401
Ratio control curve fuel actuator
0
90
402
Ratio control curve air actuator
0
90
403
Ratio control curve VSD
20 %
100 %
500
Ratio Control
501
No-flame positions fuel actuator
Index 0 = no-load position
Index 1 = pre-purge position
Index 2 = post-purge position
0
90
0
0
0
502
No-flame positions air actuator
Index 0 = no-load position
Index 1 = pre-purge position
Index 2 = post-purge position
0
90
0
65
45
*Data is for reference purposes only. Fulton Companies is not responsible for this product, including (but not limited to) its accuracy, reliability, and safety. No
Fulton document should substitute for full review of documentation available from the product manufacturer.
+Out of Test Fire
Note:
Customer settings should be recorded in the Customer column for reference.
Table 7 - Steam Program for Siemens LMV3*
Содержание VSRT 10
Страница 2: ......
Страница 5: ...1 1 Section Safety Warnings 1 Installation 2 Operation 3 Maintenance Troubleshooting 4 Warranty 5...
Страница 11: ...2 1 Section Safety Warnings 1 Installation 2 Operation 3 Maintenance Troubleshooting 4 Warranty 5...
Страница 44: ...2 INSTALLATION Fulton 2018 2 34 VSRT_IOM_2018 1213...
Страница 45: ...3 1 Section Safety Warnings 1 Installation 2 Operation 3 Maintenance Troubleshooting 4 Warranty 5...
Страница 61: ...4 1 Section Safety Warnings 1 Installation 2 Operation 3 Maintenance Troubleshooting 4 Warranty 5...
Страница 88: ...5 1 Section Safety Warnings 1 Installation 2 Operation 3 Maintenance Troubleshooting 4 Warranty 5 Parts 6...
Страница 89: ...5 WARRANTY Fulton 2018 5 2 VSRT_IOM_2018 1213...